| Plan Review Notes For Permit 21091170 |
| Permit Number |
21091170 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-04-06 16:12:56 | 3RD REVIEW FMC | | | PERMIT: 21091170 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE TAKE ANOTHER LOOK AT THE VAV-5 CALCULATIONS. | | | I BELIEVE THE NUMBERS ARE INCORRECT. THE REQUIRED | | | OUTDOOR AIR- CFM?S PER PERSON SHOULD BE 7.5 NOT 0. THE | | | REQUIRED OUTDOOR AIR- CFM?S PER FT. SHOULD BE 0.12 NOT | | | 0.06. PLEASE ADJUST AND PROVIDE THE CORRECT TOTALS. FMC | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|