2022-03-21 08:16:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 21ST/ 2021
 ACTION: DENIED
  
 1) COMPLIED.
 2) COMPLIED.
  
 3)SEMI-COMPLIED.
 3A)
  
 4B)
  
 4C) 3RD REQUEST. SEE 4D. 206.2.5 206.2.5 RESTAURANTS
 AND CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 BARS, INCLUDING RAISED OR SUNKEN DINING AREAS, AND
 OUTDOOR DINING AREAS.
  
 4D) 3RD REQUEST. PLEASE NOTE THE MAIN BAR NO LONGER HAS
 AN ACCESSIBLE SEAT AT THE BAR THAT NEEDS TO SHOW
 COMPLIANCE WITH WEST PALM BEACH DEVELOPMENT
 SERVICES-CONSTRUCTION SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 27TH/ 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 104 THE CONFERENCE ROOM NOR THE
 DIMENSIONS TO DETERMINE THE OCCUPANT LOAD. SHEET G1-1
 AREA OF WORK SHOWS THE SQ. FT. OF AREA PER ROOM BUT NOT
 THE OCCUPANT LOAD, NOR THE OCCUPANT LOAD FACTOR. 2020
 FBC-BUILDING TABLE 1005.4.
  
 2-3) COMPLIED.
  
 4A-D) COMPLIED.
  
  
 5) SHEET A4.4 NOW SHOWS A RETRACTABLE STAGE BUT THE
 PLAN DOES NOT SHOW THE HEIGHT OF THE STAGE WHEN IN THE
 HORIZONTAL POSITION, NOR COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 405.2 SLOPE, EDGE
 PROTECTION 405.9 AND POSSIBLY 405.8 HANDRAILS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER