2022-02-24 13:10:422ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091170
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.0: THE BANQUET HALL VAV-1 AND VAV-2 REQUIRE
 1017 CFM OF OUTDOOR AIR EACH. THE PROVIDED AIR FOR EACH
 SHOULD AT LEAST BE THE MINIMUM REQUIRED OUTDOOR AIR.
  
 2) PLEASE TAKE A SECOND LOOK AT VAV-3, VAV-5, VAV-7,
 VAV-9. IT APPEARS THAT THE OCCUPANCY DENSITY IS THE
 DIFFERENCE BETWEEN THE NUMBERS SHOWN ON SHEET M3.0 IN
 THESE AREAS AND THE NUMBERS THAT I CALCULATE FOR EACH
 USE OF SPACE LISTED ABOVE. PLEASE SEE THE SECOND
 SENTENCE OF SECTION 403.3.1.1 COPIED BELOW FOR YOUR
 CONVENIENCE.
  
 FBC M 403.3.1.1 : THE OCCUPANT LOAD UTILIZED FOR DESIGN
 OF THE VENTILATION SYSTEM SHALL BE NOT LESS THAN THE
 NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT
 LOAD RATE INDICATED IN TABLE 403.3.1.1. VENTILATION
 RATES FOR OCCUPANCIES NOT REPRESENTED IN TABLE
 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY
 CLASSIFICATION THAT IS MOST SIMILAR
 IN TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  