| Date |
Text |
| 2022-02-24 13:10:42 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21091170 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M3.0: THE BANQUET HALL VAV-1 AND VAV-2 REQUIRE |
| | 1017 CFM OF OUTDOOR AIR EACH. THE PROVIDED AIR FOR EACH |
| | SHOULD AT LEAST BE THE MINIMUM REQUIRED OUTDOOR AIR. |
| | |
| | 2) PLEASE TAKE A SECOND LOOK AT VAV-3, VAV-5, VAV-7, |
| | VAV-9. IT APPEARS THAT THE OCCUPANCY DENSITY IS THE |
| | DIFFERENCE BETWEEN THE NUMBERS SHOWN ON SHEET M3.0 IN |
| | THESE AREAS AND THE NUMBERS THAT I CALCULATE FOR EACH |
| | USE OF SPACE LISTED ABOVE. PLEASE SEE THE SECOND |
| | SENTENCE OF SECTION 403.3.1.1 COPIED BELOW FOR YOUR |
| | CONVENIENCE. |
| | |
| | FBC M 403.3.1.1 : THE OCCUPANT LOAD UTILIZED FOR DESIGN |
| | OF THE VENTILATION SYSTEM SHALL BE NOT LESS THAN THE |
| | NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT |
| | LOAD RATE INDICATED IN TABLE 403.3.1.1. VENTILATION |
| | RATES FOR OCCUPANCIES NOT REPRESENTED IN TABLE |
| | 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY |
| | CLASSIFICATION THAT IS MOST SIMILAR |
| | IN TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| | CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| | ENGINEERING ANALYSIS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |