| 2021-11-30 16:18:56 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091170 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M3.0: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATION IN | | | FBC M TABLE 403.3.1.1. | | | | | | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE BASED ON FBC M 403.3.1.1 AND TABLE | | | 403.3.1.1 AND NOT THE ARCHITECTURAL DRAWINGS. REMINDER: | | | FOOTNOTE A OF TABLE 403.3.1.1 ALLOWS THE DESIGNER TO | | | USE THE NET OCCUPIABLE FLOOR AREA FOR THE CALCULATIONS. | | | I ASSUME WHEN I SEE THE SQUARE FOOTAGE IN THE | | | CALCULATIONS THAT THIS IS WHAT WAS USED. THE | | | CALCULATIONS APPEAR TO BE LOW. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|