| Date |
Text |
| 2022-03-01 14:04:44 | ) 2ND REVIEW. SHEET 02 IS SIGNED AND SEALED BY ENG. |
| | GEORGE FREIJO BUT THE ORIGINAL SHEET 01 IS NOT SIGNED |
| | AND SEALED BY A DESIGN PROFESSIONAL, ONCE A DESIGN |
| | PROFESSIONAL IS INVOLVED THEY TAKE OVER THE WHOLE |
| | PROJECT BOTH SHEETS NEED THE DESIGN PROFESSIONAL |
| | ELECTRONIC SIGNATURE AND SEAL. |
| | |
| | 1ST ROUND COMMENTS. THE SUBMITTED FLOOR PLAN SHEET # 01 |
| | WAS NOT DESIGNED BY A DESIGN PROFESSIONAL, EITHER AN |
| | ARCHITECT OR ENGINEER. SINCE THE FLOOR PLAN WAS NOT |
| | DESIGNED BY A DESIGN PROFESSIONAL THE CONTRACTOR MUST |
| | TAKE OWNERSHIP OF THE PLAN. CERTIFICATION BY |
| | CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT |
| | CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |