| 2022-03-01 14:03:36 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21091150 |
| | ADD: 651 OKEECHOBEE BLVD. # 1110 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-644-3503 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MARCH 01/2022 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REVIEW. SHEET 02 IS SIGNED AND SEALED BY ENG. |
| | GEORGE FREIJO BUT THE ORIGINAL SHEET 01 IS NOT SIGNED |
| | AND SEALED BY A DESIGN PROFESSIONAL, ONCE A DESIGN |
| | PROFESSIONAL IS INVOLVED THEY TAKE OVER THE WHOLE |
| | PROJECT BOTH SHEETS NEED THE DESIGN PROFESSIONAL |
| | ELECTRONIC SIGNATURE AND SEAL. |
| | |
| | 1ST ROUND COMMENTS. THE SUBMITTED FLOOR PLAN SHEET # 01 |
| | WAS NOT DESIGNED BY A DESIGN PROFESSIONAL, EITHER AN |
| | ARCHITECT OR ENGINEER. SINCE THE FLOOR PLAN WAS NOT |
| | DESIGNED BY A DESIGN PROFESSIONAL THE CONTRACTOR MUST |
| | TAKE OWNERSHIP OF THE PLAN. CERTIFICATION BY |
| | CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT |
| | CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 2) 2ND REVIEW SHEET 01 NOT REVISED. 2020 FBC-B 2509.2 |
| | BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALLS AND CEILING PANELS IN |
| | SHOWER AREAS SHALL BE OF MATERIALS LISTED IN TABLE |
| | 2509.2 AND INSTALLED IN ACCORDANCE WITH MANUFACTURERS |
| | RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C840 AND THE MANUFACTURERS |
| | RECOMMENDATIONS. |
| | |
| | 3) 2ND REQUEST, SHEET 01 NOT REVISED. 2020 FBC-B |
| | SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS |
| | WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A |
| | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 |
| | INCHES ABOVE THE DRAIN INLET. |
| | |
| | 4-5) COMPLIED. |
| | |
| | 6) TUB ENCLOSURE WALLS AND OR SHOWER WALLS. TUB |
| | ENCLOSURE WALLS AND OR SHOWER WALLS WHICH ARE ALSO |
| | TENANT SEPARATION WALL WHICH WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH SECTION 420.2 SEPARATION WALLS AND FIRE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 708 OF THE 2020 |
| | FBC-BUILDING CODE. |
| | |
| | 7) 2ND REQUEST. THE SUBMITTED DOCUMENTS FOR FLOOR |
| | UNDERLAYMENT DOES NOT MATCH, (2) DOCUMENTS WERE |
| | SUBMITTED FOR WHISPER MAT CS (FOR TILE AND OR MARBLE) |
| | AND A 3RD DOCUMENT FOR WHISERPAD FOR LAMINATE FLOORING. |
| | |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES, NO DISCREPANCIES. |
| | |
| | THE FLOOR PLAN STATES TO REPLACE THE EXISTING FLOOR W/ |
| | NEW TILE OVER THIN SET. FLOOR INSULATION/ UNDERLAYMENT |
| | (FBC-B 2020) FOR TILE, STONE, MARBLE, VINYL LAMINATE |
| | FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE |
| | SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE |
| | FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED |
| | UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR |
| | ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 7A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 7B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 7C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |