| Plan Review Notes For Permit 21091144 |
| Permit Number |
21091144 |
|
| Review Stop |
G |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-07-26 11:45:26 | 3RD REVIEW FBC-2017 FUEL GAS | | | PERMIT- 21091144 | | | 7/26/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN | | | SHEETS DO NOT MATCH. | | | | | | A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS | | | AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT | | | DRAWING (P-242) AND THE RISER (P-505. | | | | | | B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON | | | LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE, | | | HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH | | | PIPE. WHICH IS IT? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|