Plan Review Notes
Plan Review Notes For Permit 21091144
Permit Number 21091144
Review Stop G
Sequence Number 2
Notes
Date Text
2022-02-17 14:48:052ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 2/17/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE ADDITIONAL
 INFORMATION FOR THE TWO GAS GENERATORS. IN REPONSE TO
 THE 1ST REVIEW COMMENTS LISTED BELOW, THE EOR IS
 STATING IN THE COMMENT RESPONSE NARRATIVE THAT THE
 GENERATORS ARE LEVEL 2, NOT 1. THE RISER ON SHEET P-505
 INDICATES LEVEL 2 "STAND-BY" GENERATORS. PLEASE
 INDICATE ON THE PLANS THE SPECIFIC SYSTEMS THAT THE
 GENERATORS ARE SUPPLYING POWER TO. LEVEL 1 STAND-BY
 GENERATORS ACCORDING TO SEC. 4.4.1 NFPA 110 ARE
 INSTALLED WHERE FAILURE OF THE EQUIPMENT TO PERFORM
 COULD RESULT IN LOSS OF HUMAN LIFE OR SERIOUS INJURIES.
 REFER TO SEC. 403.8.3 FBC B.- THE FOLLOWING ARE
 CLASSIFIED AS STANDBY POWER LOADS IN HIGH RISE
 BUILDINGS-
  
 1.VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT
 FOR SMOKEPROOF ENCLOSURES.
 2.ELEVATORS.
 3.WHERE ELEVATORS ARE PROVIDED IN A HIGH-RISE BUILDING
 FOR ACCESSIBLE MEANS OF EGRESS, FIRE SERVICE ACCESS OR
 OCCUPANT SELF-EVACUATION, THE STANDBY POWER SYSTEM
 SHALL ALSO COMPLY WITH SECTIONS 1009, 3007 OR 3008, AS
 APPLICABLE.
  
 SEC. 4.4.1 NFPA 110 LEVEL 1 ESSENTIAL ELECTRICAL
 SYSTEMS:
 LIFE SAFETY ILLUMINATION
 FIRE DETECTION AND ALARM SYSTEMS
 ELEVATORS
 FIRE PUMPS
 PUBLIC SAFETY COMMUNICATIONS SYSTEMS
 INDUSTRIAL PROCESSES WHERE CURRENT INTERRUPTION WOULD
 PRODUCE SERIOUS LIFE SAFETY OR HEALTH HAZARDS
 ESSENTIAL VENTILATING AND SMOKE REMOVAL SYSTEMS
  
 SEE SECTION 403.4.8.4 FBC B FOR LIST OF EMERGENCY POWER
 LOADS. PLEASE NOTE THERE ARE RELATIVE GAS COMMENTS FOR
 THE 30KW GENERATOR INSTALLATION UNDER PERMIT- 21021355.
  
 1ST REVIEW COMMENTS- 11/5/21
  
 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110
 WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO
 SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON
 LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED
 FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER
 PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO
 SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A
 BOILER.
 A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 110 AND
 SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED
 GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE
 POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE
 SEPARATE EPS SHUTOFF VALVES.
  
 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING
 PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW
 COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE
 A BUILDING SHALL BE SEPARATED FROM AREAS OF THE
 BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED
 IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE
 THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE
 RATING SHALL BE REDUCED TO 1 HOUR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  