| 2021-11-05 17:08:12 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 21091144 |
| | 11/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P505 & P110: PLEASE PLACE A NOTE ON THE PLAN |
| | INDICATING A SEPARATE PERMIT IS REQUIRED FOR THE |
| | GENERATOR ON THE ROOF. A FULL GAS REVIEW FOR THE |
| | GENERATOR IS NOT BEING PERFORMED AT THIS TIME- SECTIONS |
| | 105.1 & 107.1 WPB. |
| | |
| | 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110 |
| | WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO |
| | SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON |
| | LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED |
| | FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER |
| | PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO |
| | SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A |
| | BOILER. |
| | |
| | A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 1110 AND |
| | SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED |
| | GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE |
| | POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE |
| | SEPARATE EPS SHUTOFF VALVES. |
| | |
| | 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING |
| | PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW |
| | COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE |
| | A BUILDING SHALL BE SEPARATED FROM AREAS OF THE |
| | BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED |
| | IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE |
| | THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE |
| | RATING SHALL BE REDUCED TO 1 HOUR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |