2021-11-05 17:08:121ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 11/5/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P505 & P110: PLEASE PLACE A NOTE ON THE PLAN
 INDICATING A SEPARATE PERMIT IS REQUIRED FOR THE
 GENERATOR ON THE ROOF. A FULL GAS REVIEW FOR THE
 GENERATOR IS NOT BEING PERFORMED AT THIS TIME- SECTIONS
 105.1 & 107.1 WPB.
  
 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110
 WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO
 SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON
 LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED
 FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER
 PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO
 SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A
 BOILER.
  
 A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 1110 AND
 SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED
 GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE
 POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE
 SEPARATE EPS SHUTOFF VALVES.
  
 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING
 PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW
 COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE
 A BUILDING SHALL BE SEPARATED FROM AREAS OF THE
 BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED
 IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE
 THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE
 RATING SHALL BE REDUCED TO 1 HOUR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  