| 2021-12-06 17:47:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | REVISION DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) I SAW AN INDEX PAGE FOR THE STRUCTURAL SHEETS. |
| | HOWEVER, I DID NOT SEE A REVISED INDEX PAGE WITH THE |
| | PLAN SHEETS AND THE REVISIONS OF EACH SHEET LISTED FOR |
| | THE ARCHITECTURAL, LIFE SAFETY OR MEP PLANS. FBC |
| | 107.2.1 |
| | |
| | 2) SPECIFY THE WIND PRESSURES FOR THE ROOF TOP |
| | GENERATOR FOR THE PENTHOUSE. PROVIDE ANCHORING DETAILS |
| | AND CALCULATIONS FOR THE GENERATOR TO SHOW THAT IT WILL |
| | RESIST THE WINDLOAD PRESSURES. FBC 107.2.1.2 |
| | |
| | 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS WITH THE |
| | WEIGHT AND DIMENSIONS FOR THE PENTHOUSE GENERATOR. FBC |
| | 107.2.1 |
| | |
| | 4) CLEARLY SHOW THAT THE GENERATOR'S EXHAUST IS TEN |
| | FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1 |
| | INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR |
| | INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET |
| | (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, |
| | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, |
| | ALLEYS, PARKING LOTS AND LOADING DOCKS. |
| | |
| | 5) ON SHEET A-790 DETAIL 1, THE UNIT A KITCHEN FLOOR |
| | PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40" |
| | CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES |
| | REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 2-3/8") |
| | |
| | 6) ON SHEET A-792 DETAIL 2, THE UNIT F KITCHEN FLOOR |
| | PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40" |
| | CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES |
| | REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 3-1/2") |
| | |
| | 7) THERE WERE SOME REVISED PAGES THAT DID NOT APPEAR ON |
| | YOUR NARRATIVE, SUCH AS SHEETS A-137, A-138 AND A-139. |
| | THERE WERE ALSO SOME SHEETS ON THE NARRATIVE THAT I |
| | COULD NOT FIND IN THE REVISED PLANS SUCH AS G-9 AND |
| | G-10. FBC 107.2.1 |
| | |
| | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |