Plan Review Notes
Plan Review Notes For Permit 21091133
Permit Number 21091133
Review Stop M
Sequence Number 4
Notes
Date Text
2022-02-14 15:14:16PLEASE READ THE CODE SECTIONS FOR THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS MENTIONED BELOW AND IN
 PREVIOUS REVIEWS. I DID NOT ASK FOR THE EQUIPMENT
 SPECS. I AM ASKING YOU TO SHOW THE CALCULATIONS ON HOW
 YOU DETERMINED THAT THE UNIT YOU HAVE IS THE CORRECT
 SIZE FOR THIS HOME.
  
 PLEASE UNDERSTAND WHEN I ASK FOR THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS THAT WOULD BE A MANUAL J
 CALCULATION FOR SIZING THE MECHANICAL SYSTEM. I DO SEE
 THE ENERGY CALCULATIONS. PLEASE SUBMIT THE EQUIPMENT
 SIZING CALCULATIONS. FBC EC R403.7
  
 PLEASE SHOW THE LOCATION OF THE CINDENSING UNIT ON THE
 MECHANICAL DRAWING.FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER