| 2022-02-14 15:14:16 | PLEASE READ THE CODE SECTIONS FOR THE MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS MENTIONED BELOW AND IN | | | PREVIOUS REVIEWS. I DID NOT ASK FOR THE EQUIPMENT | | | SPECS. I AM ASKING YOU TO SHOW THE CALCULATIONS ON HOW | | | YOU DETERMINED THAT THE UNIT YOU HAVE IS THE CORRECT | | | SIZE FOR THIS HOME. | | | | | | PLEASE UNDERSTAND WHEN I ASK FOR THE MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS THAT WOULD BE A MANUAL J | | | CALCULATION FOR SIZING THE MECHANICAL SYSTEM. I DO SEE | | | THE ENERGY CALCULATIONS. PLEASE SUBMIT THE EQUIPMENT | | | SIZING CALCULATIONS. FBC EC R403.7 | | | | | | PLEASE SHOW THE LOCATION OF THE CINDENSING UNIT ON THE | | | MECHANICAL DRAWING.FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|