2022-01-25 08:13:37PLEASE UNDERSTAND WHEN I ASK FOR THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS THAT WOULD BE A MANUAL J
 CALCULATION FOR SIZING THE MECHANICAL SYSTEM. I DO SEE
 THE ENERGY CALCULATIONS. PLEASE SUBMIT THE EQUIPMENT
 SIZING CALCULATIONS. FBC EC R403.7
  
 PLEASE SHOW THE LOCATION OF THE CINDENSING UNIT ON THE
 MECHANICAL DRAWING.FBC 107.2.1
  