| Plan Review Notes For Permit 21091133 |
| Permit Number |
21091133 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-12-10 09:31:08 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091133 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SEE COMMENT 2 OF 1ST CYCLE REVIEW BELOW. | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7 | | | | | | 2) PLEASE PROVIDE A COMPLETE MECHANICAL DRAWING | | | INCLUDING THE DUCT SIZES AND THE RETURN AIR PATH FROM | | | EACH ROOM WITH A DOOR BETWEEN IT AND THE AHU. FBC | | | 107.2.1 | | | | | | 3) PLEASE SHOW HOW THE CONDENSING UNIT WILL BE | | | ANCHORED. | | | | | | 4) THE CONDENSATE CANNOT DRAIN INTO THE BUILDING DRAIN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|