2021-12-10 09:31:082ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091133
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE COMMENT 2 OF 1ST CYCLE REVIEW BELOW.
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
 2) PLEASE PROVIDE A COMPLETE MECHANICAL DRAWING
 INCLUDING THE DUCT SIZES AND THE RETURN AIR PATH FROM
 EACH ROOM WITH A DOOR BETWEEN IT AND THE AHU. FBC
 107.2.1
  
 3) PLEASE SHOW HOW THE CONDENSING UNIT WILL BE
 ANCHORED.
  
 4) THE CONDENSATE CANNOT DRAIN INTO THE BUILDING DRAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  