| Plan Review Notes For Permit 21091133 |
| Permit Number |
21091133 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-07 08:36:51 | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE | | | GARAGE CONVERSION. FBC EC 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THE NEWLY CONDITIONED GARAGE | | | CONVERSION. FBC EC R403.7 | | | | | | 3) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING ALL OF | | | THE MECHANICAL WORK FOR THIS PROJECT. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|