| 2021-12-08 10:38:08 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PREVIOUS COMMENT HAS NOT BEEN RESOLVED. THE |
| | UNDERLAYMENT LETTER FROM THE TECHNICAL SERVICES |
| | DIRECTOR OF PLITEQ INC. IS FOR FLOOR COVERING SYSTEMS |
| | AND THIS PRODUCT IS A SOUND INSULATION UNDERLAYMENT. |
| | THE TESTING THAT WAS USED IS NOT EQUIVALENT TO THE TEST |
| | REQUIRED BY ASTM E84-2016 FOR FLAME SPREAD. DUE TO |
| | THESE ISSUES I AM NOT ABLE TO ACCEPT THIS LETTER IN |
| | LIEU OF THE REQUIRED TEST REPORT. [THE TECHNICAL NOTE |
| | FOR THE GENIEMAT STATES THAT THE FLAME SPREAD IS 65 AND |
| | THE SMOKE DEVELOPED IS 105 PER ASTM E84. WE REQUIRE THE |
| | ACTUAL TEST REPORT FROM AN ACCREDITED TESTING |
| | LABORATORY. THE TECHNICAL NOTE FROM THE MANUFACTURER IS |
| | NOT ACCEPTABLE. IF THE TEST REPORT IS NOT AVAILABLE, |
| | ANOTHER SOUND INSULATION WILL BE REQUIRED.] SUBMIT THE |
| | FLAME SPREAD TEST REPORT PER ASTM E 84-09. FBC603.1 |
| | |
| | 2) IN REGARD TO THE EMAIL FROM WILSON BYRICK, THE FBC |
| | CODE SECTION 805.1.3 IS FOR INSULATING BOARDS NOT MORE |
| | THAN 1/2 INCH THICK. THE INSULATION THAT IS BEING |
| | PROPOSED IS A SHEET THAT COMES IN ROLLS AND NOT A RIGID |
| | BOARD. IF YOU ARE NOT ABLE TO PROVIDE THE REQUIRED TEST |
| | REPORTS FOR THE SOUND INSULATING UNDERLAYMENT, SELECT |
| | ANOTHER PRODUCT THAT DOES HAVE THE REQUIRED TEST |
| | REPORTS. |
| | |
| | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE |
| | REVIEW COMMENTS HAVE BEEN ADDRESSED. |