Plan Review Notes
Plan Review Notes For Permit 21091128
Permit Number 21091128
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-17 09:24:43BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THE VALUE HAS BEEN ADJUSTED TO $36,480.00 PER
 THE ICC BUILDING VALUATION DATA.
  
 1.PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
 WHERE REQUIRED BY THE BUILDING OFFICIAL OR WHERE
 GEOTECHNICAL INVESTIGATIONS INVOLVE IN-SITU TESTING,
 LABORATORY TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 BASED ON THE OFFICIAL ZONING MAP REFERRED TO IN SECTION
 53-2 OF CHAPTER 53 OF THE CITY CODE OF WEST PALM BEACH,
 FLORIDA, 1962, ADOPTED JUNE 15, 1964, YOUR PROPERTY,
 LOCATED AT 1229 PINE SAGE CIRCLE, W.P.B., FL, IS
 LOCATED IN AN AREA OF QUESTIONABLE SOILS AND REQUIRES
 INVESTIGATION BY A GEOTECHNICAL ENGINEER WITH ITS
 SUBSEQUENT SOILS REPORT AND DENSITY TESTING.
 THIS ONLY RELIEVES YOU FROM THE STATUTORY REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. THERE MAY BE OTHER
 ENTITIES, SUCH AS YOUR DESIGN PROFESSIONAL OR YOUR
 LENDING INSTITUTION THAT MAY REQUIRE THE ABOVE
 MENTIONED INVESTIGATION.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. PROVIDE SMOKE ALARMS
  
 EXISTING BUILDING
 SECTION 1104 SMOKE ALARMS
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 WHERE AN ADDITION IS MADE TO A BUILDING OR STRUCTURE OF
 A GROUP R OR I-1 OCCUPANCY, THE EXISTING BUILDING SHALL
 BE PROVIDED WITH SMOKE ALARMS AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE OR SECTION R314 OF THE
 FLORIDA BUILDING CODE, RESIDENTIAL AS APPLICABLE.
  
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 5. THE WINDOW SCHEDULE ON PLAN PAGE A102 INDICATES THE
 SAME PRODUCT APPROVAL FOR BOTH THE SINGLE HUNG AND
 HORIZONTAL SLIDER WINDOWS. FL14911-R12 IS FOR THE
 SINGLE HUNG WINDOW.
 PROVIDE A VALID FLORIDA PRODUCT APPROVAL FOR THE
 HORIZONTAL SLIDER WINDOW.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6. PROVIDE THE COVER SHEET FOR PRODUCT APPROVAL
 FL14911.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 7.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE
 R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 8.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX. DO NOT
 E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  
  
  
  