| 2022-01-11 16:36:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21091113 807 N FLAGLER DR |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 2A) SECOND REQUEST: THE WATER CLOSET SHALL BE |
| | POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO |
| | ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| | WALL OR PARTITION PER FBC ACC 604.2. |
| | TO BE CLEAR, SHOW THE CENTERLINE OF THE WATER CLOSET |
| | FROM THE SIDE WALL. |
| | |
| | 2B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | SECOND REQUEST: PROVIDE DIMENSIONS ON THE PLAN AND SHOW |
| | CLEARANCE IN GIRLS RR. |
| | |
| | 2C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL TO CENTER OF WALL ATTACHMENT (SEE FBC ACC |
| | FIGURE 604.5.1) AND |
| | SECOND REQUEST SHOW GRAB BAR EXTENDING 54 INCHES |
| | MINIMUM FROM THE REAR WALL PER FBC ACC 604.5.1 |
| | |
| | 4. MINIMUM FACILITIES; PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: |
| | NEW COMMENT: RESPONSE NOTED ON PLUMBING COMMENTS. PER |
| | WPB FBC 107.2.1, NOTE THE OCCUPANCY/OCCUPANCY LOAD AND |
| | MINIMUM FACILITY PLUMBING SCHEDULE ON THE PLANS. |
| | |
| | 5. PER WPB FBC 107.2.1, REVISE FINISH WALL SCHEDULE FOR |
| | CUSTODIAL ROOM. REFER TO FBC PL 310.3 AND FBC 1210.2.2. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT |
| | THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS |
| | THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE |
| | THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD |
| | BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| | SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | NEW COMMENT: DEFER TO BUILDING PLANS EXAMINER |
| | |
| | 7. P-6.01PER FBC PL 914.2, A CIRCUIT VENT CONNECTION |
| | SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM (CIRCUIT |
| | VENTED) FIXTURE DRAINS (FLOOR DRAINS IN THIS CASE) ON |
| | THE BRANCH SERVICING THE BOYS AND GIRLS RESTROOMS. |
| | SECOND REQUEST: PROVIDE CIRCUIT VENT CONNECTION BETWEEN |
| | THE TWO UPSTREAM FLOOR DRAINS. TO BE CLEAR, THIS CANNOT |
| | BE ACCOMPLISHED BY USING A DOUBLE WYE OR COMBINATION |
| | WYE AND EIGHTH BEND. A WYE DOWNSTREAM FOR ONE FLOOR |
| | DRAIN, THEN A COMBO ON ITS BACK FOR THE VENT THEN A |
| | COMBO UPSTREAM FOR THE SECOND FLOOR DRAIN PROVIDES THE |
| | NECESSARY CONFIGURATION. |
| | |
| | 17. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT |
| | WATER PIPING INSULATION COMPLYING WITH FBC EC TABLE |
| | C403.2.10. |
| | NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED |
| | "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL |
| | EAST SPECIFICATION 22 07 00 PLUMBING INSULATION" |
| | NEW COMMENT: PROVIDE NOTE "PROVIDE INSULATION OF |
| | PLUMBING PIPING SYSTEMS IN ACCORDANCE WITH ROSARIAN |
| | ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL EAST |
| | SPECIFICATION 22 07 00" |
| | |
| | |
| | 19. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION |
| | FOR PLUMBING PIPING SYSTEMS. SUPPORTING DOCUMENT SGM |
| | MEP IS INCOMPLETE. |
| | NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED |
| | "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL |
| | EAST SPECIFICATION 22 11 16 DOMESTIC WATER PIPING" |
| | NEW COMMENT: PROVIDE NOTE "PROVIDE PIPING SYSTEMS IN |
| | ACCORDANCE WITH ROSARIAN ACADEMY RENOVATIONS TO |
| | RESTROOM-LEWIS HALL EAST SPECIFICATION 22 11 16 |
| | DOMESTIC WATER PIPING" |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |