| Plan Review Notes For Permit 21091104 |
| Permit Number |
21091104 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-12 10:48:20 | PLEASE PROVIDE STATISTICAL DATA FOR OUR BUILDING | | | OFFICIAL TO APPROVE THE USE OF THE EXCEPTION TO FMC | | | 403.3.1.1 AS CHOSING TO USE THE ARCHITECTS EGRESS | | | NUMBERS IS NOT STATISTICAL DATA. | | | | | | AS AN ALTERNATIVE THE DESIGNER COULD USE THE EXCEPTION | | | FOR FMC 403.2 | | | | | | 403.2 OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW | | | RATE SHALL BE DETERMINED IN ACCORDANCE WITH SECTION | | | 403.3. | | | | | | EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL | | | DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM | | | DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF | | | CONTAMINANTS | | | FROM EXCEEDING THAT OBTAINABLE BY THE RATE OF OUTDOOR | | | AIR VENTILATION DETERMINED IN ACCORDANCE WITH SECTION | | | 403.3, THE MINIMUM REQUIRED RATE OF OUTDOOR AIR SHALL | | | BE REDUCED | | | IN ACCORDANCE WITH SUCH ENGINEERED SYSTEM DESIGN. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|