| Plan Review Notes For Permit 21091104 |
| Permit Number |
21091104 |
|
| Review Stop |
P-GREASE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-01 15:51:01 | 1ST REVIEW FBC-2020 PLUMBING- GREASE INTERCEPTOR. | | | PERMIT- 21091104 | | | 12/1/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P0.1, P1.1 & P3.1: PLACE A NOTE ON THE PLAN | | | INDICATING THE GREASE INTERCEPTOR WILL BE INSTALLED | | | UNDER A SEPARATE PERMIT- SECTION 105.1 & 107.1 WPB. | | | | | | 2) P0.1, P1.1, P3.1: THE CLEAR WATER WASTE FROM THE | | | HAND SINK AND THE ICE MAKER SHALL NOT DRAIN INTO THE | | | GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. | | | | | | 3) P0.1, P1.1 & P3.1: GREASE INTERCEPTOR: A) PROVIDE | | | SIZING CALCULATIONS- SECTIONS 1003.3.5 & 1003.3.7 FBC | | | P. B) PROVIDE AND EQUIPMENT SCHEDULE INDICATING THE | | | MAKE AND MODEL OF THE INTERCEPTOR, CAPACITY AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5 & | | | 1003.3.7 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|