| 2021-12-01 15:38:25 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091104 |
| | 12/1/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-400: FBC-ACC COMPLIANCE DETAILS- |
| | A) LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE |
| | DIAGRAM FOR THE WATER CLOSET- SECTION 604.3. |
| | B) LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE |
| | DIAGRAMS FOR THE LAVATORIES- 606.2. |
| | C) TURNING SPACE DIAMETER- 304.3. |
| | D) THE TOILET COMPARTMENT DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR THE LAVATORY- 603.2.3. |
| | E) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED |
| | FLOORS TO THE REFLECTIVE SURFACES- SECTION 603.3 |
| | F) PLEASE SHOW THE ACTUAL LENGTH OF THE SIDE GRAB BAR |
| | AT THE WATER CLOSET AND THE MINIMUM 54-INCH EXTENSION |
| | FROM THE REAR WALL- SECTION & FIGURE 604.5.1 & FIGURES |
| | 604.5.1 & 604.5.2. |
| | G) PLEASE SHOW THE 36 MIN. LENGTH MEASUREMENT FOR THE |
| | REAR GRAB BAR AT THE WATER CLOSET- SECTION & FIGURE |
| | 604.5.2. |
| | |
| | 2) A-410: SEE COMMENT #1 ABOVE AND SHOW COMPLIANCE FOR |
| | THE MEN'S BATHROOMS. |
| | |
| | 3) P0.1 & A4.00: PLEASE ADD THE MAKES AND MODELS OF THE |
| | DRINKING FOUNTAINS TO THE FIXTURE SPECIFICATION TABLE- |
| | SECTION 410.1 FBC P. |
| | |
| | 4) A-100, A-400: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE DRINKING |
| | FOUNTAINS- SECTION 306 FBC ACC. |
| | |
| | 5) A-100, A-400: INDICATE PROTRUSION LIMITS COMPLIANCE |
| | FOR THE DRINKING FOUNTAINS- SECTION 307.2 FBC ACC. |
| | |
| | 6) P0.1, P1.1, P3.1: THE CLEAR WATER WASTE FROM THE |
| | HAND SINK AND THE ICE MAKER SHALL NOT DRAIN INTO THE |
| | GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. |
| | |
| | 7) P0.1, P1.1 & P3.1 GREASE INTERCEPTOR: A) PROVIDE |
| | SIZING CALCULATIONS- SECTIONS 1003.3.5 & 1003.3.7 FBC |
| | P. B) PROVIDE AND EQUIPMENT SCHEDULE INDICATING THE |
| | MAKE AND MODEL OF THE INTERCEPTOR, CAPACITY AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5 & |
| | 1003.3.7. C) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED |
| | FOR INSTALLATION OF THE INTERCEPTOR. |
| | |
| | 8) P1.1 & P3.1: URINALS ARE NOT INCLUDED IN THE |
| | DEFINITION OF BATHROOM GROUP AND THEIR DRAINS CANNOT |
| | CONNECT TO A HORIZONTAL WET VENT- SECTIONS 202 & 912.1 |
| | FBC P. IN ORDER FOR THE HWC DOWNSTREAM OF THE URINAL TO |
| | BE VENTED TO CODE, THE HWC DRAIN CONNECTION MUST BE |
| | RELOCATED TO A POINT DOWNSTREAM OF THE URINAL BRANCH |
| | CONNECTION TO THE 4-INCH DRAIN. |
| | |
| | 9) P2.1 & P3.3: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- 419.5 FBC P. |
| | |
| | 10) P2.1 & P3.3: REFER TO TABLE 608.3 FBC P AND PROVIDE |
| | AN EQUIPMENT SCHEDULE FOR THE REQUIRED BACKFLOW |
| | PREVENTERS FOR SUPPLY LINES TO THE DISHWASHER, ICE |
| | MAKER, AND THE ICE TEA AND COFFEE BREWERS. PLEASE |
| | PROVIDE A BF SYMBOL AT THE DISHWASHER. |
| | |
| | 11) P0.2: PLEASE PROVIDE THE EFFICIENCY RATING OF THE |
| | WATER HEATER AND SUBMIT MANUFACTURERS SPECIFICATIONS- |
| | TABLE C404.2 FBC EC. REVISE THE ENERGYGAUGE REPORT TO |
| | INCLUDE THE COMPLIANCE DATA FOR THE WATER HEATER AND |
| | PIPING- C101.5.1. |
| | |
| | 12) A1.10: IT APPEARS THAT ROOF DRAINAGE PLANS AND |
| | CALCULATIONS FOR THE LOWER ENTRANCE CANOPIES HAVE NOT |
| | BEEN PROVIDED. PLEASE INDICATE HOW STORMWATER FROM |
| | THESE AREAS WILL DRAIN TO APPROVED PLACES OF DISPOSAL- |
| | SECTION 1101.2 FBC P. |
| | |
| | 13) A1.10: PLEASE SHOW ON THE CIVIL PLANS THE DISCHARGE |
| | LOCATIONS OF THE DOWNSPOUTS TO APPROVED DRAINAGE |
| | LOCATIONS SUCH STORM DRAINS, CATCH BASINS OR TO GRADED |
| | AREAS- SECTION 1101.2 FBC P. |
| | |
| | 14) A5.30: PROVIDE THE DIMENSIONS OF THE SCUPPERS- |
| | SECTION 1108.3 FBC P. |
| | |
| | 15) A5.40 & P0.1: PROVIDE THE MAKE AND MODEL OF THE |
| | ROOF DRAIN ASSEMBLY AND ADD IT TO THE FIXTURE SCHEDULE- |
| | SECTION 1105.1 FBC P. |
| | |
| | 16) A5.30: PROVIDE DOWNSPOUT CONNECTION SUPPORT AND |
| | TERMINATION DETAILS. PLEASE NOTE THE SPOUTS SHALL |
| | TERMINATE NOT LESS THAN 1 FT. FROM THE BUILDING- 1101.6 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |