| 2021-11-22 08:42:08 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21091104 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING |
| | THAT THE KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION, DOCUMENTS AND PLAN REVIEW AS THEY WILL NOT |
| | BE REVIEWED UNDER THIS PERMIT. FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE OUTDOOR AIR CALCULATIONS USING FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1. THE SPECTATOR AREAS |
| | APPEAR TO BE LOW. |
| | |
| | 3) SHEET M1.1 PLEASE SHOW THE FIRE DAMPERS IN THE RATED |
| | WALLS SEPARATING THE STAGE FROM THE STORAGE AREAS. FBC |
| | M 607 |
| | |
| | 4) SHEET M1.1: PLEASE SHOW THE FIRE DAMPER FOR THE |
| | EXHAUST DUCT LEAVING THE MOP SINK AREA IN THE KITCHEN. |
| | FBC M 607 |
| | |
| | 5) PLEASE PROVIDE THE CONDENSATE DRAINAGE PIPING |
| | DIAGRAM INCLUDING PIPE MATERIAL, SIZES AND OUTDOOR |
| | TERMINATION LOCATION. FBC M 307 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |