| 2022-07-11 10:31:37 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21091104 |
| | 7/11/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLAN SHEET K301 DETAIL 1 IS LABELED WATER & GAS PLAN |
| | HOWEVER NO GAS APPLIANCES ARE IDENTIFIED ON THE |
| | DRAWING. PLEASE PROVIDE A GAS APPLIANCE EQUIPMENT |
| | LAYOUT PLAN AND EQUIPMENT SCHEDULE- SEC. 107.2.1 WPB. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL NEW |
| | APPLIANCES AND EQUIPMENT- SECTIONS 305.1 AND 623.1 FBC |
| | FG. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL NEW |
| | GAS-FIRED APPLIANCES AND EQUIPMENT AND INDICATE HOW THE |
| | AIR WILL BE SUPPLIED- SECTION 304.1 FBC FG. |
| | |
| | 4) PROVIDE A COMPLETE GAS RISER DRAWING- SEC. |
| | 107.3.5.1.5 WPB. THE RISER SHALL INCLUDE THE FOLLOWING |
| | ITEMS: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |