| Plan Review Notes For Permit 21091083 |
| Permit Number |
21091083 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-11 06:16:01 | 1ST PP MECHANICAL AUDIT FBC-2020 MECHANICAL | | | PERMIT-21091083 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | AUDIT RESULTS: DENIED. | | | | | | 1) THE DRYER EXHAUST DUCT SHALL MEET FBC RES M1502.4.1. | | | IT MUST BE 4 INCH NOMINAL IN DIAMETER. | | | | | | | | | M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A | | | SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL | | | HAVING A | | | MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE). THE DUCT | | | SHALL BE 4 INCHES (102 MM) NOMINAL IN DIAMETER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|