2022-02-11 06:16:011ST PP MECHANICAL AUDIT FBC-2020 MECHANICAL
 PERMIT-21091083
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 AUDIT RESULTS: DENIED.
  
 1) THE DRYER EXHAUST DUCT SHALL MEET FBC RES M1502.4.1.
 IT MUST BE 4 INCH NOMINAL IN DIAMETER.
  
  
 M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A
 SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL
 HAVING A
 MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE). THE DUCT
 SHALL BE 4 INCHES (102 MM) NOMINAL IN DIAMETER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  