| 2022-04-13 11:19:06 | ELECTRICAL REVIEW FAILED |
| | 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, |
| | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR |
| | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 |
| | 2) PLEASE DETAIL INTERIOR LOCATIONS FOR ELECTRIC |
| | PANELS. FBC 107.2 |
| | 3) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE |
| | DISCONNECTS AND METERS. FBC 107.2 |
| | 4) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AS PER NEC |
| | 210.50 (E), 210.63 AND 210.64 |
| | 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AS PER NEC |
| | 210.50 (E), 210.63 AND 210.64 |
| | 6) PLEASE PROVIDE AN ACCURATE SCOPE OF WORK. FBC107.2 |
| | 7) PLEASE DETAIL SMOKE ALARMS AS REQUIRED. FBC RE 2020, |
| | 7TH EDITION |
| | 8) PLEASE DETAIL ALL RECEPTACLES REQUIRED AS PER NEC |
| | 250.50 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |