| 2022-06-03 10:21:32 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 21091077 |
| | REVIEWED: JUNE 3, 2022 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,7TH EDITION (2020) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1. THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. WHERE LOCATED IN A WALL, THE OPENING SHALL BE |
| | NOT LESS THAN 22 INCHES WIDE BY 30 INCHES HIGH (559 MM |
| | WIDE BY 762 MM HIGH). WHERE THE ACCESS IS LOCATED IN A |
| | CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC |
| | SPACE SHALL BE 30 INCHES (762 MM) AT SOME POINT ABOVE |
| | THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF |
| | CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR |
| | ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. |
| | - PLEASE SHOW ATTIC ACCESS LOCATION ON PLANS |
| | |
| | 2. 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| | IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| | LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (2 PERCENT). |
| | - PROVIDE LANDING AT EXTERIOR SIDE OF DOOR IF GREATER |
| | THAN 2 RISERS PROVIDED. |
| | |
| | 3. 318 FBC[R] INDICATE THE MEANS OF TERMITE PROTECTION |
| | PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS. |
| | |
| | 4. 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET |
| | REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE |
| | METHOD IN R401.2 AND SUPPLY DOCUMENTATION. |
| | - PLEASE SUPPLY ENERGY CALCULATIONS FOR THE NEWLY |
| | ENCLOSED SPACE AND NEWLY INSULATED ATTIC. |
| | 5. 806.2 FBC[R] THE MINIMUM NET FREE VENTILATING AREA |
| | SHALL BE 1/150 OF THE AREA OF THE VENTED SPACE. |
| | - SEE EXECPTIONS IN SECTION 806.2 TO ALLOW 1/300. |
| | |
| | 6. ASCE 7-10 26.7.1 WIND EXPOSURE CATEGORY. |
| | - PLEASE PROVIDE PROJECT DATA, OR INDICATE WHERE THIS |
| | IS ON THE PLANS. |
| | OCCUPANCY = R3 |
| | BASIC WIND SPEED=170 |
| | RISK CATEGORY = II |
| | EXPOSURE CATEGORY = B |
| | BUILDING CLASSIFICATION = ENCLOSED |
| | MEAN BLDG. HGT. = 0?-0? ? THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK. |
| | WIND SPEED V ULT = 170 |
| | WIND SPEED V ASD = 132 |
| | |
| | 7. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWAND DOOR |
| | |
| | 8. R302.1 EXTERIOR WALLS |
| | - PLEASE PROVIDE THE DISTANCE OF ENCLOSED SPACE TO THE |
| | PROPERTY LINE. THIS CAN BE ON THE SURVEY THAT ZONING |
| | WANTS AS WELL. |
| | |
| | NOTES: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |