2022-06-03 10:21:32BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21091077
 REVIEWED: JUNE 3, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. WHERE LOCATED IN A WALL, THE OPENING SHALL BE
 NOT LESS THAN 22 INCHES WIDE BY 30 INCHES HIGH (559 MM
 WIDE BY 762 MM HIGH). WHERE THE ACCESS IS LOCATED IN A
 CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC
 SPACE SHALL BE 30 INCHES (762 MM) AT SOME POINT ABOVE
 THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF
 CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
 - PLEASE SHOW ATTIC ACCESS LOCATION ON PLANS
  
 2. 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED
 IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR
 LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2 PERCENT).
 - PROVIDE LANDING AT EXTERIOR SIDE OF DOOR IF GREATER
 THAN 2 RISERS PROVIDED.
  
 3. 318 FBC[R] INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
  
 4. 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 - PLEASE SUPPLY ENERGY CALCULATIONS FOR THE NEWLY
 ENCLOSED SPACE AND NEWLY INSULATED ATTIC.
 5. 806.2 FBC[R] THE MINIMUM NET FREE VENTILATING AREA
 SHALL BE 1/150 OF THE AREA OF THE VENTED SPACE.
 - SEE EXECPTIONS IN SECTION 806.2 TO ALLOW 1/300.
  
 6. ASCE 7-10 26.7.1 WIND EXPOSURE CATEGORY.
 - PLEASE PROVIDE PROJECT DATA, OR INDICATE WHERE THIS
 IS ON THE PLANS.
 OCCUPANCY = R3
 BASIC WIND SPEED=170
 RISK CATEGORY = II
 EXPOSURE CATEGORY = B
 BUILDING CLASSIFICATION = ENCLOSED
 MEAN BLDG. HGT. = 0?-0? ? THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK.
 WIND SPEED V ULT = 170
 WIND SPEED V ASD = 132
  
 7. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWAND DOOR
  
 8. R302.1 EXTERIOR WALLS
 - PLEASE PROVIDE THE DISTANCE OF ENCLOSED SPACE TO THE
 PROPERTY LINE. THIS CAN BE ON THE SURVEY THAT ZONING
 WANTS AS WELL.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  