| Permit Number |
21091067 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-29 15:56:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL | | | PROPOSED TILE PRODUCT. | | | | | | TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT | | | CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE | | | VINYL/LAMINATE ETC AND IS MANUFACTURED AROUND THE WORLD | | | AND NOT ALL ARE TESTED AND MEETING LISTED AND NFPA | | | STANDARDS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC | | | TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED | | | FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING. | | | | | | | | | 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|