| 2021-10-28 17:15:19 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091049 |
| | 10/28/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101: PROVIDE A SANITARY WASTE AND VENT |
| | ISOMETRIC DRAWING FOR THE NEW BREAKROOM FIXTURES AND |
| | NEW HUB DRAIN IN THE OLD BREAKROOM- SECTION 107.2.1 & |
| | 107.3.5.1.3 WPB. PROVIDE A FLOOR PLAN DIAGRAM SHOWING |
| | THE NEW DRAIN PIPE POINTS OF CONNECTION TO THE EXISTING |
| | BUILDING DRAIN- SECTION 107.2.1 WPB. |
| | |
| | 2) P101: PROVIDE A WATER RISER DRAWING THAT INCLUDES |
| | THE LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS AND |
| | BACKFLOW PREVENTERS FOR THE SUPPLY LINES TO THE ICE AND |
| | WATER DISPENSER- SECTIONS 604.9 AND 608.3 FBC P. |
| | |
| | 3) P001: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTION |
| | 107.2.1 WPB. |
| | |
| | 4) A012: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS AT THE NEW BREAKROOM SINK- SECTION 606.2 AND |
| | 305 FBC ACC. |
| | |
| | 5) A012: PROVIDE THE WIDTH OF THE COUNTER AT THE SINK- |
| | SECTION 308 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |