2021-10-28 17:15:191ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091049
 10/28/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P101: PROVIDE A SANITARY WASTE AND VENT
 ISOMETRIC DRAWING FOR THE NEW BREAKROOM FIXTURES AND
 NEW HUB DRAIN IN THE OLD BREAKROOM- SECTION 107.2.1 &
 107.3.5.1.3 WPB. PROVIDE A FLOOR PLAN DIAGRAM SHOWING
 THE NEW DRAIN PIPE POINTS OF CONNECTION TO THE EXISTING
 BUILDING DRAIN- SECTION 107.2.1 WPB.
  
 2) P101: PROVIDE A WATER RISER DRAWING THAT INCLUDES
 THE LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS AND
 BACKFLOW PREVENTERS FOR THE SUPPLY LINES TO THE ICE AND
 WATER DISPENSER- SECTIONS 604.9 AND 608.3 FBC P.
  
 3) P001: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTION
 107.2.1 WPB.
  
 4) A012: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS AT THE NEW BREAKROOM SINK- SECTION 606.2 AND
 305 FBC ACC.
  
 5) A012: PROVIDE THE WIDTH OF THE COUNTER AT THE SINK-
 SECTION 308 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  