| 2022-08-02 14:40:22 | NEW WAREHOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE OVERHEAD DOORS. |
| | |
| | 2) PLEASE PROVIDE DETAILS FOR THE ALUMINUM CANOPIES TO |
| | COMPLY WITH THE WIND LOADS - FBC 1609.1 - OR LIST THE |
| | CANOPIES TO BE A DEFERRED SUBMITTAL ON THE DRAWINGS FBC |
| | WPB 107.3.4.1 |
| | |
| | 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOFING SYSTEM OR LIST THE |
| | ROOFING TO BE A DEFERRED SUBMITTAL ON THE DRAWINGS FBC |
| | WPB 107.3.4.1 |
| | |
| | 4) ROOFING SYSTEM PRODUCT APPROVALS, AWNING SHOP |
| | DRAWINGS AND WINDOW AND DOOR PRODUCT APPROVALS MAY BE |
| | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON |
| | THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 5) PARKING LOT SHALL BE A SEPARATE PERMIT - FBC A |
| | 208.3.1 PARKING SPACES COMPLYING WITH 502 THAT SERVE A |
| | PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE |
| | SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE |
| | COMPLYING WITH 206.4. ALL SPACES MUST BE LOCATED ON AN |
| | ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118 MM) |
| | WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR |
| | WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER |
| | OWN VEHICLE. |
| | |
| | 6) THE SIGNED AND SEALED "PRODUCT APPROVAL WORK SHEET" |
| | DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |
| | |