| 2021-11-03 15:10:47 | 11/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-2; |
| | |
| | A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND |
| | CALCULATION OF THE SQUARE FOOTAGE CONVERTED TO GALLONS |
| | PER MINUTES PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WHERE IS THE STORM WATER DARING TO. WOULD YOU PLEASE |
| | SHOW ON THE CIVIL DRAWINGS PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. ON CORE PLAN ONE AND TWO WOULD YOU PLEASE SHOW THE |
| | CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORY, TURNING |
| | RADIUS AND TOILET PER THE 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE. |
| | |
| | 2. ON SHEET P-1; |
| | |
| | A. THERE ARE RAIN WATER LEADER SHOWN FOR THE STORM. |
| | WOULD PLEASE PROVIDE AN ISOMETRIC WITH SIZE OF PIPES |
| | AND THE SIZE OF ROOF DRAINS PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | C. ON THE ISOMETRIC THERE IS NO MAIN SHUT-OFF INTO THE |
| | STRUCTURE. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING |
| | THROUGH RATED WALLS. PLEASE SUBMIT THE COMPLETE |
| | ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB AMENDMENTS |
| | TO FBC SEC. 107.2.1 |
| | |
| | 3. ON SHEET IR-1; UNDER BACKFLOW A PRESSURE VACUUM |
| | BREAKER SHOWN BUT THE CITY OF WEST PALM BEACH UTILITIES |
| | DEPARTMENT AND THEIR CROSS CONNECTION PROGRAM ONLY |
| | ALLOW A REDUCED ZONE PRESSURE VACUUM BREAKER. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 4. ON SHEET IR-2; |
| | |
| | A. THE IRRIGATION HAS A PRESSURE VACUUM BREAKER SHOWN |
| | BUT THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT |
| | AND THEIR CROSS CONNECTION PROGRAM ONLY ALLOW A REDUCED |
| | ZONE PRESSURE VACUUM BREAKER. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. THE RZP WILL REQUIRE A SEPARATE PERMIT BY A LICENSED |
| | CONTRACTOR AND CERTIFIED BY THE CITY OF WEST PALM BEACH |
| | UTILITIES DEPARTMENT. WOULD YOU PLEASE ADD THIS ON THE |
| | PAGE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |