| Plan Review Notes For Permit 21091012 |
| Permit Number |
21091012 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-06 16:27:32 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21091012 | | | 10/6/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) WATER LINE: PLEASE PROVIDE MORE DETAILS ON THE PLAN | | | FOR THE NEW WATER LINE INSTALLATION. SHOW THE TYPES AND | | | SIZES OF HOT AND COLD WATER PIPING, AND THE PIPING RUNS | | | FROM THE POINTS OF CONNECTION TO THE NEW PLUMBING | | | FIXTURES- SECTION 107.2.1 WPB. BASED ON THE DRAWINGS, | | | IT APPEARS THAT THE NEW SINK, DISHWASHER, AND | | | REFRIGERATER ICE MAKER WILL BE SUPPLIED BY THE LINES. | | | PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE REQUIRED | | | FOR SUPPLY LINES TO THE DISHWASHER AND ICE MAKER- | | | SECTION P2903.5 FBC RES. | | | | | | 2) PROVIDE A SANITARY DRAINAGE AND VENT PIPING | | | ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|