2021-10-06 16:27:321ST REVIEW FBC-2020 RES.
 PERMIT- 21091012
 10/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WATER LINE: PLEASE PROVIDE MORE DETAILS ON THE PLAN
 FOR THE NEW WATER LINE INSTALLATION. SHOW THE TYPES AND
 SIZES OF HOT AND COLD WATER PIPING, AND THE PIPING RUNS
 FROM THE POINTS OF CONNECTION TO THE NEW PLUMBING
 FIXTURES- SECTION 107.2.1 WPB. BASED ON THE DRAWINGS,
 IT APPEARS THAT THE NEW SINK, DISHWASHER, AND
 REFRIGERATER ICE MAKER WILL BE SUPPLIED BY THE LINES.
 PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE REQUIRED
 FOR SUPPLY LINES TO THE DISHWASHER AND ICE MAKER-
 SECTION P2903.5 FBC RES.
  
 2) PROVIDE A SANITARY DRAINAGE AND VENT PIPING
 ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  