| 2022-04-28 17:58:55 | 4TH REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090964 |
| | 4/28/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISED SHEETS A3 & MP1: THE REVISED PLANS SHOWING A |
| | NEW INSTA-HOT WATER HEATER IN THE EXISTING STORAGE TANK |
| | WATER HEATER ARE NOT IN COMPLIANCE WITH THE FOLLOWING |
| | CODE SECTIONS- |
| | |
| | A) SEC. 502.5: 30X30-INCH CLEAR WORKING SPACE ON THE |
| | CONTROL SIDE OF THE INSTA-HOT FOR SERVICE ACCESS NOT |
| | PROVIDED. |
| | |
| | B) SEC. 502.1 FBC P & TABLE C404.2 FBC EC: INSTA-HOT |
| | EQUIPMENT SCHEDULED NOT PROVIDED ON THE PLAN- MAKE, |
| | MODEL, EFFICIENCY RATING. |
| | |
| | C) SEC. 607.2 FBC P & 107.3.5.1.3 WPB: A HWR LINE |
| | SYMBOL NOT PROVIDED ON THE RISER ON LAYOUT DRAWING. IT |
| | APPEARS THE RETURN LINE HAS THE HW LINE SYMBOL AND THE |
| | LINE IS FEEDING DIRECTLY INTO THE COLD WATER INLET OF |
| | THE SMALL TANK WATER HEATER. TYPICALLY, THE HWR |
| | CONNECTS TO THE COLD WATER INLET PIPE OF THE WATER |
| | HEATER. |
| | |
| | D) SEC. C404.1 FBC EC: THE 1/2-INCH HW LAVATORY FIXTURE |
| | PIPES ARE EXCEEDING THE MAXIMUM 2FT. ALLOWABLE LENGTH |
| | FROM THE HOT WATER SOURCE. IN ORDER TO BE COMPLIANT THE |
| | LOOP SHALL EXTEND DOWN IN THE WALL TO THE LAV FIXTURE |
| | SUPPLY PIPE LOCATION. |
| | |
| | 2) SHEETS A2, A3, AND E-1 DO NOT MATCH WITH THE OTHER |
| | PLANS BECAUSE THE INSTA-HOT IN THE CLOSET IS NOT SHOWN- |
| | SEC. 107.2.1 WPB. |
| | |
| | 3) SHEET A1: PLEASE CORRECT THE NOTE AT THE WATER |
| | HEATER SPECIFYING A ASSE 1070 TEMPERED WATER MIXING |
| | VALVE AT THE WATER HEATER. A TEMPERED WATER MIXING |
| | VALVE IS ONLY NEEDED AT THE LAVATORIES PER SECS. 419.5 |
| | & 607.2.1 FBC P. IF INSTALLING A MASTER THERMOSTATIC |
| | MIXING VALVE AT THE WATER HEATER IT SHALL BE LISTED FOR |
| | LIMITING THE TEMPERATURE OF HOT WATER TO THE FIXTURES |
| | PER SECTION 607.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE CONTACT ME IF YOU HAVE |
| | QUESTIONS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |