| 2022-03-01 11:26:20 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090964 |
| | 3/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MP-1 & A-3: THE REQUIRED SERVICE SINK IS NOT |
| | SHOWN ON THE PLANS, RISERS, OR IN THE FIXTURE SCHEDULE- |
| | TABLE 403.1 FBC P. |
| | |
| | 2) MP-1: PLEASE REVISE KEYNOTE 2 TO INDICATE THE |
| | TEMPERED WATER WILL DELIVERED AT A TEMPERATURE BETWEEN |
| | 85 DEGREES AND 110 DEGREES F. HOT WATER IS DEFINED AS |
| | WATER AT A TEMPERATURE OF 110 DEGREES F AND ABOVE. |
| | |
| | 3) A-3: THE RISER DRAWINGS DO NOT SHOW THE PLUMBING |
| | PIPING FOR THE NEW DRINKING FOUNTAINS- SEC. 107.2.1 |
| | WPB. |
| | |
| | 4) A-3: THE SANITARY AND WATER RISERS DO NOT MATCH. THE |
| | SANITARY RISER SHOWS ONE LAVATORY, ONE WATER CLOSET AND |
| | TWO SINKS. THE WATER RISER SHOWS TWO LAVATORIES AND ONE |
| | WATER CLOSET- SEC. 107.2.1 WPB. PLEASE USE THE L-1 OR |
| | S-1 LABELS AS SHOW IN THE FIXTURE SCHEDULE TO IDENTIFY |
| | THE FIXTURES. |
| | |
| | 5) A-3: THE SANITARY RISER IS STILL SHOWING THE FIXTURE |
| | DRAIN FROM THE NEW SINK MAKING A PROHIBITED CONNECTION |
| | INT THE BATHROOM WET VENT- SEC. 912.1 FBC P. |
| | |
| | 6) A-3: PLEASE SHOW THE RECIRCULATION LINE AND LOOP IN |
| | THE WATER RISER- SEC. 607.2 FBC P. |
| | |
| | 7) MP-1 & A-3: PLEASE NOTE THAT THE THERMOSTAT ON THE |
| | WATER HEATER SHALL NOT SERVE AS THE WATER TEMPERATURE |
| | LIMITING MEANS FOR ALL FIXTURES THAT REQUIRE HOT WATER |
| | SUCH AS THE NEW S-1 SINK. THE HOT WATER TEMPERATURE |
| | SHALL BE CONTROLLED BY A MASTER THERMOSTATIC MIXING |
| | VALVE AT THE WATER HEATER OR AT THE LOCALLY AT THE |
| | SINK- SEC. 607.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE CONTACT ME IF YOU HAVE |
| | QUESTIONS. |
| | |