Plan Review Notes
Plan Review Notes For Permit 21090964
Permit Number 21090964
Review Stop P
Sequence Number 3
Notes
Date Text
2022-03-01 11:26:203RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21090964
 3/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1 & A-3: THE REQUIRED SERVICE SINK IS NOT
 SHOWN ON THE PLANS, RISERS, OR IN THE FIXTURE SCHEDULE-
 TABLE 403.1 FBC P.
  
 2) MP-1: PLEASE REVISE KEYNOTE 2 TO INDICATE THE
 TEMPERED WATER WILL DELIVERED AT A TEMPERATURE BETWEEN
 85 DEGREES AND 110 DEGREES F. HOT WATER IS DEFINED AS
 WATER AT A TEMPERATURE OF 110 DEGREES F AND ABOVE.
  
 3) A-3: THE RISER DRAWINGS DO NOT SHOW THE PLUMBING
 PIPING FOR THE NEW DRINKING FOUNTAINS- SEC. 107.2.1
 WPB.
  
 4) A-3: THE SANITARY AND WATER RISERS DO NOT MATCH. THE
 SANITARY RISER SHOWS ONE LAVATORY, ONE WATER CLOSET AND
 TWO SINKS. THE WATER RISER SHOWS TWO LAVATORIES AND ONE
 WATER CLOSET- SEC. 107.2.1 WPB. PLEASE USE THE L-1 OR
 S-1 LABELS AS SHOW IN THE FIXTURE SCHEDULE TO IDENTIFY
 THE FIXTURES.
  
 5) A-3: THE SANITARY RISER IS STILL SHOWING THE FIXTURE
 DRAIN FROM THE NEW SINK MAKING A PROHIBITED CONNECTION
 INT THE BATHROOM WET VENT- SEC. 912.1 FBC P.
  
 6) A-3: PLEASE SHOW THE RECIRCULATION LINE AND LOOP IN
 THE WATER RISER- SEC. 607.2 FBC P.
  
 7) MP-1 & A-3: PLEASE NOTE THAT THE THERMOSTAT ON THE
 WATER HEATER SHALL NOT SERVE AS THE WATER TEMPERATURE
 LIMITING MEANS FOR ALL FIXTURES THAT REQUIRE HOT WATER
 SUCH AS THE NEW S-1 SINK. THE HOT WATER TEMPERATURE
 SHALL BE CONTROLLED BY A MASTER THERMOSTATIC MIXING
 VALVE AT THE WATER HEATER OR AT THE LOCALLY AT THE
 SINK- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE CONTACT ME IF YOU HAVE
 QUESTIONS.
  