| Date |
Text |
| 2022-02-02 13:26:18 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090964 |
| | 2/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAP LETTERS. PLEASE NOTE THAT THE BUILDING PLANS |
| | EXAMINER DISGAGREES WITH THE OCCUPANT LOAD |
| | CLASSIFICATION OF B FOR THE NEW COUNTER AREA 100 AND IS |
| | STATING THAT IT IS AN M. THE FOLLOWING REVIEW IS BASED |
| | ON THE CURRENT SET OF PLANS RESUBMITTED HOWEVER IF THE |
| | CLASSIFICATION IS REVISED TO INDICATE M THERE MAY BE |
| | ADDITIONAL COMMENTS. |
| | |
| | 1) FAILED. SHEET A-1: A COMPLETE PLUMBING REVIEW OF THE |
| | PROJECT CANNOT BE COMPLETED WITHOUT PLUMBING FIXTURE |
| | CALCULATIONS. THE PLANS APPEAR TO INDICATE A PARTIAL |
| | CHANGE OF OCCUPANCY FROM STORAGE TO MERCANTILE |
| | (SALES-SHOWROOM)- SEE SECTIONS 309.1 FBC B, AND SECTION |
| | 1010.1 FBC EX. REFER TO TABLE 403.1 FBC P AND PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | PLUMBING FIXTURES. PLEASE NOTE THAT SERVICE SINKS AND |
| | DRINKING FOUNTAINS ARE REQUIRED, AND SEPARATE TOILET |
| | FACILITIES FOR MALE AND FEMALE USE UNLESS MEETING THE |
| | EXCEPTIONS UNDER SECTION 403.2 FBC P. THE PLAN SHOWS 17 |
| | OCCUPANTS. AS PREVIOUSLY NOTED, DRINKING FOUNTAINS AND |
| | SERVICE SINK ARE REQUIRED- TABLE 403.1E AND SEC. 410.2 |
| | FBC P. REVISE THE CALCULATIONS AND PLANS TO SHOW THE |
| | FIXTURE LOCATIONS AND PLUMBING PIPING DETAILS. |
| | |
| | 2) FAILED. SHEET A-3: THE NEW SINK IN THE SALES AREA |
| | REQUIRES A SEPARATE VENT AND THE SINK FIXTURE DRAIN |
| | MUST CONNECT TO THE MAIN SANITARY AT A POINT DOWNSTREAM |
| | OF THE WET VENT FOR THE NEW TOILET ROOM- SECTION 912.1 |
| | CORRECTION WAS NOT MADE- THE RISER IS STILL |
| | NON-COMPLIANT- SEC. 912.1 FBC P. |
| | |
| | 3) FAILED. A-3 & MP-1: INDICATE HOW TEMPERED WATER WILL |
| | BE PROVIDED TO THE NEW LAVATORY- SECTION 416.5 FBC P. |
| | IF A MIXING VALVE IS TO BE USED PLEASE LIST THE MAKE |
| | AND MODEL AND VERIFY IT IS ASSE 1070 APPROVED- SECTION |
| | 607.1.2 FBC P. TEMPERED WATER IS DEFINED AS WATER WITH |
| | A TEMPERATURE RANGE BETWEEN 85 DEGREES F AND 110 |
| | DEGREES F. A MASTER MIXING VALVE CANNOT BE USED BECAUSE |
| | ONLY THE LAVATORY REQUIRES TEMPERED WATER AND THE OTHER |
| | SINKS REQUIRE HOT WATER AT 110 DEGREES F AND ABOVE. |
| | REMOVE THE MASTER MIXING VALVE AND SHOW A MIXING VALVE |
| | AT THE LAVATORY TO MEET COMPLIANCE. |
| | |
| | 6) FAILED. MP-1: PLEASE INCLUDE THE SALES SINK IN THE |
| | PLUMBING FIXTURE SCHEDULE- SECTION 308 FBC ACC, AND |
| | 422.1 FBC P. TWO SINKS ARE SHOWN IN THE RISER ON A3 AND |
| | ON THE MP-1 BUT ONLY S-1 IS SHOWN IN THE SCHEDULE. |
| | PLEASE IDENTIFY THE SECOND SINK- SEC. 107.2.1 WPB. |
| | |
| | 7H) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2 (DETAIL IS NOT IN COMPLIANCE WITH FIGURE |
| | 306.3- KNEE CLEARANCE WIDTH AND HEIGHT NOT SHOWN). NOT |
| | PROVIDED. |
| | |
| | 8) FAILED. DRINKING FOUNTAINS WHERE REQUIRED: REFER TO |
| | SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING |
| | FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS |
| | SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND |
| | SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. CLEAR |
| | FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE |
| | WHEELCHAIR ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC. |
| | INDICATE COMPLIANCE WITH SECTION 307.2 PROTRUSION |
| | LIMITS. NOT PROVIDED- SEE COMMENT #1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |