Plan Review Notes
Plan Review Notes For Permit 21090964
Permit Number 21090964
Review Stop M
Sequence Number 2
Notes
Date Text
2022-02-08 15:45:40MECHANICAL RESPONSE FOR NOTE 2 AND 3 ARE NOT ON SHEET
 MP-1 ADDRESSING THE 1ST CYCLE MECHANICAL REVIEW
 COMMENTS BELOW:
  
 PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE IN THIS TENANT SPACE.
  
 PLEASE SHOW CONDENSATE PIPING MATERIAL AND TERMINATION
 LOCATION FOR NEW RTU.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER