Plan Review Notes
Plan Review Notes For Permit 21090964
Permit Number 21090964
Review Stop B
Sequence Number 2
Notes
Date Text
2022-01-26 11:24:58WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090964
 ADD: 2611 MERCER AVE.
 CONT: ABACO BUILDERS
 TEL: 561-575-5393
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 26TH/ 2021
 ACTION: DENIED
  
 1) SHEET A-1 PROJECT DATA:
 1A) 2ND REQUEST. CITY ELECTRIC SUPPLY HAS AN ELECTRICAL
 WHOLESALE NETWORK ACROSS THE USA AND CANADA. WHEN YOU
 LOOK AT THE DEFINITION OF MERCANTILE (2020
 FBC-BUILDING) SECTION 309.1 RETAIL OR WHOLESALE
 FACILITIES ARE INCLUDED UNDER THE OCCUPANCY OF
 MERCANTILE.
  
 1ST ROUND COMMENTS. LIST THE OCCUPANCY AS BUSINESS
 OCCUPANCY. PLEASE NOTE THIS IS A CHANGE OF OCCUPANCY,
 FORMERLY STORAGE OCCUPANCY. THE PROJECT DATA LIST THE
 OCCUPANCY TYPE AS BUSINESS OCCUPANCY. BUSINESS
 OCCUPANCIES ARE USUALLY OFFICES FOR PROFESSIONALS OR
 SERVICE TYPES TRANSACTIONS, IT CAN BE ARGUED THE
 OCCUPANCY TYPE IS MERCANTILE SINCE THERE IS A LARGE
 AREA VACANT BUT INDICATES COUNTER AREA. NEITHER THE A-1
 SHEET NOR THE LIFE SAFETY SHEET REALLY DEFINE THE OPEN
 SALES AREA WELL. 2020 FBC-BUILDING CODE SECTION 304.1
 VERSES SECTION 309.1 MERCANTILE AND SALES ROOMS.
  
 1B) 2ND REQUEST. PLEASE UPDATE THE OCCUPANCY TYPE AND
 OCCUPANT LOAD. MERCANTILE OCCUPANCY THE OCCUPANT LOAD
 WILL INCREASE FROM 10 (BUSINESS) TO 25 MERCANTILE 1498
 SQ. FT./ 60= 25 OCCUPANTS.
 1ST ROUND OF COMMENTS. THE OCCUPANT LOAD DOES NOT
 INDICATE THE SQUARE FOOTAGE OF THE AREA UNDERGOING THE
 CHANGE OF OCCUPANCY?107. 2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1C) 2ND REVIEW. WITH THE PREVIOUS OCCUPANT LOAD COUNT
 BEING LESS THAN 15 A UNI-SEX RESTROOM COULD BE CODE
 COMPLIANT, BUT WITH THE NEW OCCUPANT LOAD FOR
 MERCANTILE OF 25 OCCUPANTS SEPARATE RESTROOM FACILITIES
 WILL BE REQUIRED. PLEASE REVIEW SECTION 2902.2 OF THE
 2020 FBC-BUILDING CODE.
 1ST ROUND OF COMMENTS. THE OCCUPANT LOAD DECLARED IS
 USING THE OCCUPANT LOAD FACTOR OF 100 SQ. FT./ OCCUPANT
 SUPPOSED BUSINESS OCCUPANCY. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE TABLE 1004.5, THE OCCUPANT LOAD
 FACTOR FOR A BUSINESS OCCUPANCY IS CURRENTLY 150 SQ.
 FT./ OCCUPANT. NOTE FOR MERCANTILE OCCUPANCY THE
 OCCUPANT LOAD FACTOR IS 60 SQ. FT./ OCCUPANT TABLE
 1004.5 OF THE 2020 FBC-BUILDING CODE.
  
 1D)(1) 2ND REQUEST. WITH THE INCREASED OCCUPANT LOAD
 FOR A MERCANTILE OCCUPANCY OF 25 OCCUPANTS THE
 REQUIREMENT FOR DRINKING FOUNTAINS PER TABLE 2902.1
 REQUIRING DRINKING FOUNTAINS UNLESS COMPLIANCE CAN BE
 MET BY SECTION 2902.5.
 1ST ROUND OF COMMENTS. THE PLUMBING FIXTURE COUNT IS
 GOING TO VARY DEPENDING ON THE OCCUPANCY
 CLASSIFICATION. FOR THIS REVIEW A MERCANTILE OCCUPANCY
 WILL BE FIGURED SIMILAR TO AUTO ZONE WHERE THERE ARE
 MERCANTILE SHELVING RACKS IN THE FRONT PORTION, SALES
 /TRANSACTION COUNTERS AND WAREHOUSE SECTION BEHIND THE
 COUNTERS. THE PROPOSED TENANT IS CITY ELECTRIC SUPPLY.
  
 1D)(2) NEW COMMENT. 2020 FBC-ACCESSIBILITY CODE. 211.3
 MORE THAN MINIMUM NUMBER. WHERE MORE THAN THE MINIMUM
 NUMBER OF DRINKING FOUNTAINS SPECIFIED IN 211.2 ARE
 PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF DRINKING
 FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 1D)(3) NEW COMMENT. PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 1D)(4) NEW COMMENT. 602.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 1D)(5) NEW COMMENT. SPOUT OUTLETS/ DRINKING FOUNTAINS.
 2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 1E-F) COMPLIED.
  
 1G) NEW COMMENT. THE FLOOR PLAN SHOW THE OCCUPANCY
 SEPARATION WALL ONE HOUR AND DOOR NUMBER 3 WITH NOTE TO
 HAVE SELF CLOSING DEVISE AND MEET ADA STANDARDS.
 DISCREPANCY DOOR # 3 IN THE DOOR SCHEDULE STATES
 PASSAGE SET HARDWARE/ 1 HR. RATED. DISCREPANCY. 2020
 FBC-B SECTION 716.5.9 FIRE DOORS, CLOSING.
  
 2) COMPLIED.
  
 3) SHEET A-3 ELEVATIONS:
 3A-B) COMPLIED.
  
 3C)2ND REQUEST. 1 HOUR FIRE RATED STUD UL LISTING U 465
 MISSING INFORMATION THE MINIMUM GAUGE FOR THE FIRE
 RATING AND MAXIMUM LENGTH OF FIRE RATED STUD? PROVIDE
 THE ACTUAL UL LISTING ON THE PLANS, THE INSPECTOR DOES
 NOT HAVE A BOOK OF UL LISTINGS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) CHANGE OF OCCUPANCY MAY REQUIRE IMPACT FEE
 ASSESSMENT. IMPACT FEES - DIGITAL SUBMITTALS: PLANS
 WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY
 VIA PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  