| 2021-11-08 09:38:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090964 |
| | 11/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-1: A COMPLETE PLUMBING REVIEW OF THE PROJECT |
| | CANNOT BE COMPLETED WITHOUT PLUMBING FIXTURE |
| | CALCULATIONS. THE PLANS APPEAR TO INDICATE A PARTIAL |
| | CHANGE OF OCCUPANCY FROM STORAGE TO MERCANTILE |
| | (SALES-SHOWROOM)- SEE SECTIONS 309.1 FBC B, AND SECTION |
| | 1010.1 FBC EX. REFER TO TABLE 403.1 FBC P AND PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | PLUMBING FIXTURES. PLEASE NOTE THAT SERVICE SINKS AND |
| | DRINKING FOUNTAINS ARE REQUIRED, AND SEPARATE TOILET |
| | FACILITIES FOR MALE AND FEMALE USE UNLESS MEETING THE |
| | EXCEPTIONS UNDER SECTION 403.2 FBC P. |
| | |
| | 2) SHEET A-3: THE NEW SINK IN THE SALES AREA REQUIRES A |
| | SEPARATE VENT AND THE SINK FIXTURE DRAIN MUST CONNECT |
| | TO THE MAIN SANITARY AT A [POINT DOWNSTREAM OF THE WET |
| | VENT FOR THE NEW TOILET ROOM- SECTION 912.1 FBC P. |
| | |
| | 3) A-3 & MP-1: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED TO THE NEW LAVATORY- SECTION 416.5 FBC P. IF A |
| | MIXING VALVE IS TO BE USED PLEASE LIST THE MAKE AND |
| | MODEL AND VERIFY IT IS ASSE 1070 APPROVED- SECTION |
| | 607.1.2 FBC P. |
| | |
| | 4) MP-1: PROVIDE THE TYPE AND THICKNESS OF HOT WATER |
| | PIPE INSULATION- TABLE C403.5.3 FBC EC. |
| | |
| | 5) MP-1: REFER TO TABLE C404.5.1 FBC EC- THE 1/2-INCH |
| | HW PIPING TO THE LAVATORIES IS EXCEEDING THE MAXIMUM 2 |
| | FT. LENGTH ALLOWABLE FROM THE HW SOURCE (WATER HEATER). |
| | PROVIDE EITHER A RECIRCULATION PUMP OR A POINT OF USE |
| | WATER HEATER. |
| | |
| | 6) MP-1: PLEASE INCLUDE THE SALES SINK IN THE PLUMBING |
| | FIXTURE SCHEDULE- SECTION 308 FBC ACC, AND 422.1 FBC P. |
| | |
| | 7) A-1 & A-3: MISSING AND INCORRECT DETAILS PER THE FBC |
| | ACCESSIBILITY CODE: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3. |
| | D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOORS- SECTION 604.4. (DETAILS SHOW MEASUREMENT IS NOT |
| | TO THE SEAT). |
| | E) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 (DETAIL SHOWS |
| | MEASUREMENT IS NOT TO THE REFLECTIVE SURFACE). |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. (DETAILS SHOW- A. REAR GRAB |
| | IS NON-COMPLIANT. B. SIDE GRAB DOES INDICATE THE |
| | MINIMUM 54-INCH EXTENSION FROM THE REAR WALL. C. |
| | HEIGHTS ARE NOT SHOWN TO THE TOPS OF THE GRIPPING |
| | SURFACES). |
| | G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. (DETAIL DOES NOT SHOW THE LOCATION ON |
| | THE OPEN SIDE). |
| | H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 (DETAIL IS NOT IN COMPLIANCE WITH FIGURE 306.3- |
| | KNEE CLEARANCE WIDTH AND HEIGHT NOT SHOWN). |
| | |
| | 8) DRINKING FOUNTAINS WHERE REQUIRED: REFER TO SECTIONS |
| | 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN |
| | INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE |
| | AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| | SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD WHEELCHAIR APPROACH TO THE WHEELCHAIR |
| | ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC. INDICATE |
| | COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | 9) A-1 & A-3, SALES SINK: A) SHOW THE CLEAR FLOOR SPACE |
| | DIAGRAM AND DIMENSIONS FOR EITHER A FORWARD OR PARALLEL |
| | APPROACH- SECTION 606.3. B) PROVIDE AN ELEVATION DETAIL |
| | SHOWING THE SINK RIM POR COUNTER HEIGHT (IF |
| | UNDERMOUNT), AND THE REQUIRED KNEE AND TOES CLEARANCES |
| | IF A FORWARD APPROACH IS TO BE USED- SECTIONS 606.2 & |
| | 606.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |