2021-11-08 09:38:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21090964
 11/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: A COMPLETE PLUMBING REVIEW OF THE PROJECT
 CANNOT BE COMPLETED WITHOUT PLUMBING FIXTURE
 CALCULATIONS. THE PLANS APPEAR TO INDICATE A PARTIAL
 CHANGE OF OCCUPANCY FROM STORAGE TO MERCANTILE
 (SALES-SHOWROOM)- SEE SECTIONS 309.1 FBC B, AND SECTION
 1010.1 FBC EX. REFER TO TABLE 403.1 FBC P AND PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 PLUMBING FIXTURES. PLEASE NOTE THAT SERVICE SINKS AND
 DRINKING FOUNTAINS ARE REQUIRED, AND SEPARATE TOILET
 FACILITIES FOR MALE AND FEMALE USE UNLESS MEETING THE
 EXCEPTIONS UNDER SECTION 403.2 FBC P.
  
 2) SHEET A-3: THE NEW SINK IN THE SALES AREA REQUIRES A
 SEPARATE VENT AND THE SINK FIXTURE DRAIN MUST CONNECT
 TO THE MAIN SANITARY AT A [POINT DOWNSTREAM OF THE WET
 VENT FOR THE NEW TOILET ROOM- SECTION 912.1 FBC P.
  
 3) A-3 & MP-1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE NEW LAVATORY- SECTION 416.5 FBC P. IF A
 MIXING VALVE IS TO BE USED PLEASE LIST THE MAKE AND
 MODEL AND VERIFY IT IS ASSE 1070 APPROVED- SECTION
 607.1.2 FBC P.
  
 4) MP-1: PROVIDE THE TYPE AND THICKNESS OF HOT WATER
 PIPE INSULATION- TABLE C403.5.3 FBC EC.
  
 5) MP-1: REFER TO TABLE C404.5.1 FBC EC- THE 1/2-INCH
 HW PIPING TO THE LAVATORIES IS EXCEEDING THE MAXIMUM 2
 FT. LENGTH ALLOWABLE FROM THE HW SOURCE (WATER HEATER).
 PROVIDE EITHER A RECIRCULATION PUMP OR A POINT OF USE
 WATER HEATER.
  
 6) MP-1: PLEASE INCLUDE THE SALES SINK IN THE PLUMBING
 FIXTURE SCHEDULE- SECTION 308 FBC ACC, AND 422.1 FBC P.
  
 7) A-1 & A-3: MISSING AND INCORRECT DETAILS PER THE FBC
 ACCESSIBILITY CODE:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3.
 D) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOORS- SECTION 604.4. (DETAILS SHOW MEASUREMENT IS NOT
 TO THE SEAT).
 E) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3 (DETAIL SHOWS
 MEASUREMENT IS NOT TO THE REFLECTIVE SURFACE).
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. (DETAILS SHOW- A. REAR GRAB
 IS NON-COMPLIANT. B. SIDE GRAB DOES INDICATE THE
 MINIMUM 54-INCH EXTENSION FROM THE REAR WALL. C.
 HEIGHTS ARE NOT SHOWN TO THE TOPS OF THE GRIPPING
 SURFACES).
 G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6. (DETAIL DOES NOT SHOW THE LOCATION ON
 THE OPEN SIDE).
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 (DETAIL IS NOT IN COMPLIANCE WITH FIGURE 306.3-
 KNEE CLEARANCE WIDTH AND HEIGHT NOT SHOWN).
  
 8) DRINKING FOUNTAINS WHERE REQUIRED: REFER TO SECTIONS
 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE WHEELCHAIR
 ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC. INDICATE
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
  
 9) A-1 & A-3, SALES SINK: A) SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSIONS FOR EITHER A FORWARD OR PARALLEL
 APPROACH- SECTION 606.3. B) PROVIDE AN ELEVATION DETAIL
 SHOWING THE SINK RIM POR COUNTER HEIGHT (IF
 UNDERMOUNT), AND THE REQUIRED KNEE AND TOES CLEARANCES
 IF A FORWARD APPROACH IS TO BE USED- SECTIONS 606.2 &
 606.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY