2021-11-10 14:30:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090964
 ADD: 2611 MERCER AVE.
 CONT: ABACO BUILDERS
 TEL: 561-575-5393
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 10TH/ 2021
 ACTION: DENIED
  
 1) SHEET A-1 PROJECT DATA:
 1A) LIST THE OCCUPANCY AS BUSINESS OCCUPANCY. PLEASE
 NOTE THIS IS A CHANGE OF OCCUPANCY, FORMERLY STORAGE
 OCCUPANCY. THE PROJECT DATA LIST THE OCCUPANCY TYPE AS
 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES ARE USUALLY
 OFFICES FOR PROFESSIONALS OR SERVICE TYPES
 TRANSACTIONS, IT CAN BE ARGUED THE OCCUPANCY TYPE IS
 MERCANTILE SINCE THERE IS A LARGE AREA VACANT BUT
 INDICATES COUNTER AREA. NEITHER THE
 A-1 SHEET NOR THE LIFE SAFETY SHEET REALLY DEFINE THE
 OPEN SALES AREA WELL. 2020 FBC-BUILDING CODE SECTION
 304.1 VERSES SECTION 309.1 MERCANTILE AND SALES ROOMS.
  
 1B) THE OCCUPANT LOAD DOES NOT INDICATE THE SQUARE
 FOOTAGE OF THE AREA UNDERGOING THE CHANGE OF
 OCCUPANCY?107. 2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) THE OCCUPANT LOAD DECLARED IS USING THE OCCUPANT
 LOAD FACTOR OF 100 SQ. FT./ OCCUPANT SUPPOSED BUSINESS
 OCCUPANCY. PLEASE REVIEW THE 2020 FBC-BUILDING CODE
 TABLE 1004.5, THE OCCUPANT LOAD FACTOR FOR A BUSINESS
 OCCUPANCY IS CURRENTLY 150 SQ. FT./ OCCUPANT. NOTE FOR
 MERCANTILE OCCUPANCY THE OCCUPANT LOAD FACTOR IS 60 SQ.
 FT./ OCCUPANT TABLE 1004.5 OF THE 2020 FBC-BUILDING
 CODE.
  
 1D) THE PLUMBING FIXTURE COUNT IS GOING TO VARY
 DEPENDING ON THE OCCUPANCY CLASSIFICATION. FOR THIS
 REVIEW A MERCANTILE OCCUPANCY WILL BE FIGURED SIMILAR
 TO AUTO ZONE WHERE THERE ARE MERCANTILE SHELVING RACKS
 IN THE FRONT PORTION, SALES /TRANSACTION COUNTERS AND
 WAREHOUSE SECTION BEHIND THE COUNTERS. THE PROPOSED
 TENANT IS CITY ELECTRIC SUPPLY.
  
 1E) ENGINEERING DATA LIST THE OCCUPANCY TYPE AS R3,
 SINGLE FAMILY RESIDENCES. PLEASE CORRECT.
  
 1F) THE FLOOR PLAN SHOWS A BACK-WALL DIMENSION OF
 7FEET. CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH (FINISHES MAY ENCROACH) ON THE FINISH
 DIMENSION!!!
  
 2) THE LIFE SAFETY SHEET DESIGN DATA THE MAXIMUM
 CAPACITY SIGN READS FOR ONE EXIT: THE MAIN ENTRANCE
 DOOR IN EACH SPACE WITH A CAPACITY OF 50 OR MORE
 OCCUPANTS. PLEASE CORRECT, SEE THE 2020 FBC-BUILDING
 CODE TABLE 1006.2.1 B OCCUPANCY WITH ONE EXIT OR EXIT
 ACCESS DOORWAY MAXIMUM OCCUPANT LOAD OF SPACE 49
 OCCUPANTS.
  
 3) SHEET A-3 ELEVATIONS:
 3A) BOTH ELEVATIONS 1 & 3 SHOW THE GRAB BARS
 DIMENSIONED FROM CENTERLINE TO THE FINISH FLOOR. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3B) BOTH ELEVATIONS 1 & 2 SHOW LAVATORY PIPES EXPOSED.
 2020 FBC-ACCESSIBILITY CODE SECTION 606.5 EXPOSED PIPES
 AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 3C) 1 HOUR FIRE RATED STUD UL LISTING U 465 MISSING
 INFORMATION THE MINIMUM GAUGE FOR THE FIRE RATING AND
 MAXIMUM LENGTH OF FIRE RATED STUD? 107.2.1.2.
  
 4) CHANGE OF OCCUPANCY MAY REQUIRE IMPACT FEE
 ASSESSMENT. IMPACT FEES - DIGITAL SUBMITTALS: PLANS
 WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY
 VIA PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved