| 2021-10-06 16:15:10 | REROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21090963 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- TPO ROOF SYSTEMS NOA 18-0109.09 SUBMITTED: CLEARLY |
| | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | 1609.1 FBC-BUILDING. NOTE: IF THE SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA. ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE |
| | USED IF THEY DON'T MEET THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. |
| | |
| | 2- NEED TO SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING |
| | AS REQUIRED BY THE CITY POLICY FOR ALL ROOFING PERMITS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- TPO ROOF SYSTEMS NOA 18-0109.09 SUBMITTED IS FOR |
| | WOOD DECKS. ROOFING FASTENER NOA 18-0308.04 IS NOT FOR |
| | WOOD DECKS. REVISE AS REQUIRED. IT IS NOT CLEAR WHAT |
| | MATERIAL IS THE ROOF DECK. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: VERIFY ROOF DECK TYPE AND PROVIDE CORRECT PRODUCT |
| | APPROVAL TO AVOID CONFLICTS/DELAYS. CHECK LIMITATIONS |
| | ON LAST PAGE OF NOA. ADDITIONAL INFORMATION MAY BE |
| | REQUIRED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |