| 2021-10-01 15:40:56 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21090948 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING |
| | THAT THE HOODS WILL NEED A SEPARATE PERMIT APPLICATION, |
| | DRAWINGS AND REVIEW AS THEY WILL NOT BE REVIEWED UNDER |
| | THIS PERMIT. |
| | |
| | 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING |
| | THAT THE REFRIGERATION SYSTEMS WILL NEED A SEPARATE |
| | PERMIT APPLICATION, DRAWINGS AND REVIEW AS THEY WILL |
| | NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) PLEASE SHOW THAT THE RETURN AIR GRILLES IN THE |
| | KITCHEN ARE AT LEAST 10 FEET AWAY FROM THE COOKING |
| | APPLIANCES IN THE KITCHEN. FBC M 601.5 EXCEPTION 1 |
| | |
| | 4) PLEASE SHOW THE FIRE DAMPER AT THE WALL OF THE |
| | ELECTRICAL ROOM WHERE THE BATH EXHAUST DUCT PENETRATES |
| | THE RATED WALL. FBC M 607 |
| | |
| | 5) PLEASE MAKE SURE THE CURRENT FBC M 2020 EDITION IS |
| | REFERENCED IN THE OUTDOOR AIR CALCULATIONS. |
| | |
| | 6) PLEASE EXPLAIN THE RETURN GRILLE IN THE ELECTRICAL |
| | ROOM. |
| | |
| | 7) IT APPEARS THAT EF 1 AND EF 2 ARE IN SINGLE STALL |
| | BATHROOMS. WHY ARE THEY EACH EXHAUSTING 370 CFM? SHEET |
| | 6.1 FAN SCHEDULE INDICATES THAT THERE EXHAUST 370 CFM. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |