| Plan Review Notes For Permit 21090948 |
| Permit Number |
21090948 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-23 15:49:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) LIFE SAFETY SHEET - WITHIN THE LOBBY THERE IS AN | | | INDICATION OF A TABLE/PLANTER WITH CHAIRS DIRECTLY | | | OBSTRUCTING A DOUBLE DOOR WITH AN EXIT SIGN LEADING TO | | | THE EXTERIOR PATIO. | | | | | | PLEASE REVIEW AND CORRECT AND PROVIDE A CLEAR PATH OF | | | TRAVEL TO THIS EXIT. | | | | | | | | | 2) LIFE SAFETY SHEET - WITHIN THE CAFE, THERE IS AN | | | INDICATION OF EXIT SIGN OVER A DOUBLE DOOR LEADING TO | | | THE EXTERIOR PATIO. | | | | | | THERE IS NO DIMENSION PROVIDED BETWEEN THE EXIT DOOR | | | AND PROPOSED TABLE AND CHAIR LOCATION. | | | | | | FOR THE REOCORD AND CODE COMPLIANCE PLEASE PROVIDE THAT | | | DIMENSION. | | | | | | | | | | | | 3) MECHANICAL/KITCHEN EQUIPMENTSHEETS - THE PROPSOED | | | HOOD AND SUSPRESSION SYSTEMS SHALL BE SUBMITTED UNDER | | | SPEARATE PERMITS & SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|