Plan Review Notes
Plan Review Notes For Permit 21090944
Permit Number 21090944
Review Stop P
Sequence Number 2
Notes
Date Text
2021-11-04 16:26:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090944 360 S ROSEMARY AVE #200
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.NEW COMMENT: P-601/DETAIL 7; APPLIANCE BOX TO
 REFRIGERATOR SHALL BE TAG IB2 W/WATER HAMMER ARRESTOR,
 NOT IB1. FBC PL 604.9 WATER HAMMER
  
 2.REGARDING THE WATER HAMMER ARRESTORS, PER WPB FBC
 107.2.1, PLEASE PROVIDE A PDI SIZE
 SCHEDULE/SPECIFICATION (SECOND REQUEST) AND TAG THE
 WATER HAMMER ARRESTORS SHOWN ON THE WATER RISER DIAGRAM
 THE APPROPRIATE SIZE. THIS IS NOT REQUIRED FOR THE IB2
 GUY GRAY APPLIANCE BOXES.
  
 3.P-601/DETAIL 7; PER WPB FBC 107.2.1, COORDINATE
 P-601/DETAIL 7 WATER TO REFRIGERATOR WITH P-202
 BACKFLOW PREVENTER SCHEDULE AND P-202/NOTE 12. DETAIL
 AS DRAWN WOULD REQUIRE A LF7R DUAL CHECK VALVE, NOT A
 LF289 VACUUM BREAKER.
  
 4.P-202 NOTES 10, 11 AND 12 CALL FOR STAINLESS STEEL
 TUBING CONNECTIONS. PER FBC PL TABLE 604.5, THIS
 PRODUCT IS NOT PERMITTED IN IN WATER DISTRIBUTION;
 STAINLESS STEEL PIPE CONFORMING TO ASTM A312 OR ASTM
 778 IS ALLOWED BUT THIS IS A MINIMUM SCHEDULE
 10/SCHEDULE 40 FOR WELDED OR THREADED APPLICATIONS. FBC
 PL 605.6 ALLOWS ACCESSIBE FLEXIBLE CONNECTORS
 CONFORMING TO ASME A112.18.6/CSA B125.6 OR COPPER OR
 COPPER-ALLOY TUBING (TYPE K, WK, L, WL, M OR WM)
 CONFORMING TO ASTM B75; ASTM B88; ASTM B251; ASTM B447
 PER FBC PL TABLE 604.5/ FBC PL TABLE 604.5.
  
 5.P-202 AND P-601/DETAIL 3; DETAIL SHOWS WATER HEATER
 ABOVE MOP BASIN, P-202 SHOWS AT OPPOSITE END OF THE
 ROOM. PER WPB FBC 107.2.1, CLARIFY.
  
 6.P-202 AND P-601/DETAIL 3; DETAIL SHOWS RELIEF LINE
 AND PAN DRAIN EACH INDEPENDENTLY DISCHARGING TO AN
 APPROVED LOCATION. PER WPB FBC 107.2.1, PROVIDE ACTUAL
 TERMINATION FOR THE DRAINS ON THE DETAIL. THE FOLLOWING
 ARE ACCEPTABLE.
 ?A) FBC PL 504.6(5)(10); (5) DISCHARGE RELIEF LINE TO
 THE FLOOR (NOT RECOMMENDED FOR THIS INSTALLATION), TO
 THE PAN SERVING THE WATER HEATER OR STORAGE TANK, TO A
 WASTE RECEPTOR OR TO THE OUTDOORS; (10)TERMINATE NOT
 MORE THAN 6 INCHES (152 MM) ABOVE AND NOT LESS THAN TWO
 TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR
 FLOOD LEVEL RIM OF THE WASTE RECEPTOR.
 ?B) FBC PL 504.7.2 THE PAN DRAIN SHALL EXTEND FULL SIZE
 AND TERMINATE OVER A SUITABLY LOCATED INDIRECT WASTE
 RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE EXTERIOR OF
 THE BUILDING AND TERMINATE NOT LESS THAN 6 INCHES (152
 MM) AND NOT MORE THAN 24 INCHES (610 MM) ABOVE THE
 ADJACENT GROUND SURFACE.
 ?C) PLEASE NOTE THAT PER FBC PL CHAPTER 2, DEFINITIONS,
 A WASTE RECEPTOR IS DEFINED AS A FLOOR SINK, STANDPIPE,
 HUB DRAIN OR FLOOR DRAIN THAT RECEIVES THE DISCHARGE OF
 ONE OR MORE INDIRECT WASTE PIPES. THE MOP
 RECEPTOR/BASIN DOES NOT QUALIFY AS A WASTE RECEPTOR.
 ?D) PER WPB FBC PROVIDE REQUIRED TRAPPED AND VENTED
 WASTE RECEPTOR ON P-202 PLUMBING PLANS RISER AND PLAN
 VIEW
  
  
 7.THE INDIVIDUAL VENTS FOR THE FLOOR SINK (SECOND
 REQUEST) AND THE TWO (2) ADDED FLOOR DRAINS ARE NOT
 COMPLIANT. VENTS SHALL CONNECT ABOVE THE CENTERLINE OF
 THE DRAIN OF THE HORIZONTAL DRAIN AND SHALL RISE
 VERTICALLY TO A POINT NOT LESS THAN 6 INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 BEING VENTED PER FBC PL 905.3 AND 905.4.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  