| | 21090944 360 S ROSEMARY AVE #200 |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.NEW COMMENT: P-601/DETAIL 7; APPLIANCE BOX TO |
| | REFRIGERATOR SHALL BE TAG IB2 W/WATER HAMMER ARRESTOR, |
| | NOT IB1. FBC PL 604.9 WATER HAMMER |
| | |
| | 2.REGARDING THE WATER HAMMER ARRESTORS, PER WPB FBC |
| | 107.2.1, PLEASE PROVIDE A PDI SIZE |
| | SCHEDULE/SPECIFICATION (SECOND REQUEST) AND TAG THE |
| | WATER HAMMER ARRESTORS SHOWN ON THE WATER RISER DIAGRAM |
| | THE APPROPRIATE SIZE. THIS IS NOT REQUIRED FOR THE IB2 |
| | GUY GRAY APPLIANCE BOXES. |
| | |
| | 3.P-601/DETAIL 7; PER WPB FBC 107.2.1, COORDINATE |
| | P-601/DETAIL 7 WATER TO REFRIGERATOR WITH P-202 |
| | BACKFLOW PREVENTER SCHEDULE AND P-202/NOTE 12. DETAIL |
| | AS DRAWN WOULD REQUIRE A LF7R DUAL CHECK VALVE, NOT A |
| | LF289 VACUUM BREAKER. |
| | |
| | 4.P-202 NOTES 10, 11 AND 12 CALL FOR STAINLESS STEEL |
| | TUBING CONNECTIONS. PER FBC PL TABLE 604.5, THIS |
| | PRODUCT IS NOT PERMITTED IN IN WATER DISTRIBUTION; |
| | STAINLESS STEEL PIPE CONFORMING TO ASTM A312 OR ASTM |
| | 778 IS ALLOWED BUT THIS IS A MINIMUM SCHEDULE |
| | 10/SCHEDULE 40 FOR WELDED OR THREADED APPLICATIONS. FBC |
| | PL 605.6 ALLOWS ACCESSIBE FLEXIBLE CONNECTORS |
| | CONFORMING TO ASME A112.18.6/CSA B125.6 OR COPPER OR |
| | COPPER-ALLOY TUBING (TYPE K, WK, L, WL, M OR WM) |
| | CONFORMING TO ASTM B75; ASTM B88; ASTM B251; ASTM B447 |
| | PER FBC PL TABLE 604.5/ FBC PL TABLE 604.5. |
| | |
| | 5.P-202 AND P-601/DETAIL 3; DETAIL SHOWS WATER HEATER |
| | ABOVE MOP BASIN, P-202 SHOWS AT OPPOSITE END OF THE |
| | ROOM. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 6.P-202 AND P-601/DETAIL 3; DETAIL SHOWS RELIEF LINE |
| | AND PAN DRAIN EACH INDEPENDENTLY DISCHARGING TO AN |
| | APPROVED LOCATION. PER WPB FBC 107.2.1, PROVIDE ACTUAL |
| | TERMINATION FOR THE DRAINS ON THE DETAIL. THE FOLLOWING |
| | ARE ACCEPTABLE. |
| | ?A) FBC PL 504.6(5)(10); (5) DISCHARGE RELIEF LINE TO |
| | THE FLOOR (NOT RECOMMENDED FOR THIS INSTALLATION), TO |
| | THE PAN SERVING THE WATER HEATER OR STORAGE TANK, TO A |
| | WASTE RECEPTOR OR TO THE OUTDOORS; (10)TERMINATE NOT |
| | MORE THAN 6 INCHES (152 MM) ABOVE AND NOT LESS THAN TWO |
| | TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR |
| | FLOOD LEVEL RIM OF THE WASTE RECEPTOR. |
| | ?B) FBC PL 504.7.2 THE PAN DRAIN SHALL EXTEND FULL SIZE |
| | AND TERMINATE OVER A SUITABLY LOCATED INDIRECT WASTE |
| | RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE EXTERIOR OF |
| | THE BUILDING AND TERMINATE NOT LESS THAN 6 INCHES (152 |
| | MM) AND NOT MORE THAN 24 INCHES (610 MM) ABOVE THE |
| | ADJACENT GROUND SURFACE. |
| | ?C) PLEASE NOTE THAT PER FBC PL CHAPTER 2, DEFINITIONS, |
| | A WASTE RECEPTOR IS DEFINED AS A FLOOR SINK, STANDPIPE, |
| | HUB DRAIN OR FLOOR DRAIN THAT RECEIVES THE DISCHARGE OF |
| | ONE OR MORE INDIRECT WASTE PIPES. THE MOP |
| | RECEPTOR/BASIN DOES NOT QUALIFY AS A WASTE RECEPTOR. |
| | ?D) PER WPB FBC PROVIDE REQUIRED TRAPPED AND VENTED |
| | WASTE RECEPTOR ON P-202 PLUMBING PLANS RISER AND PLAN |
| | VIEW |
| | |
| | |
| | 7.THE INDIVIDUAL VENTS FOR THE FLOOR SINK (SECOND |
| | REQUEST) AND THE TWO (2) ADDED FLOOR DRAINS ARE NOT |
| | COMPLIANT. VENTS SHALL CONNECT ABOVE THE CENTERLINE OF |
| | THE DRAIN OF THE HORIZONTAL DRAIN AND SHALL RISE |
| | VERTICALLY TO A POINT NOT LESS THAN 6 INCHES ABOVE THE |
| | FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE |
| | BEING VENTED PER FBC PL 905.3 AND 905.4. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |