| 2021-11-03 16:16:41 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21090944 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | | THE 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 YOU MUST | | | USE THE TABLE FOR THE OCCUPANT COUNT IN EACH SPACE AND | | | NOT THE ARCHITECTURAL COUNT. PLEASE ALSO SEPARATE THE | | | CORRIDORS FROM THE OTHER SPACES. | | | | | | 2) PLEASE SHOW THE TERMINATION LOCATION OF THE | | | CONDENSATE DRAINAGE. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|