Plan Review Notes
Plan Review Notes For Permit 21090944
Permit Number 21090944
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-20 07:17:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090944 360 S ROSEMARY AVE #200
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE: A0.02
 PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ...A) PER FBC PL 604.8.1.1WHEELCHAIR ACCESSIBLE
 COMPARTMENTS SHALL BE 60 INCHES WIDE MINIMUM MEASURED
 PERPENDICULAR TO THE SIDE WALL, AND 56 INCHES DEEP
 MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES DEEP
 MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL.
 ......1A) SPECIFIED WATER CLOSETS ARE FLOOR MOUNTED.
 PER WPB FBC 107.2, SHOW COMPLIANCE IN DETAIL 2/A0.02
 ...B) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ......1B)PER WPB FBC 107.2, REMOVE 6 INCH DIMENSION
 BETWEEN SIDE WALL AND GRAB BAR IN DETAIL 2/A0.02
 ...C) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER PER FBC ACC 604.8.
 ...D) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT, NOT TO THE RIM. SEATS SHALL NOT BE SPRUNG TO
 RETURN TO A LIFTED POSITION PER FBC ACC 604.4.
 ...E) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO
 THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED
 IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER
 CLOSET.
 ......1E) SEE MENS ADA RM 209; PER WPB FBC 107.2, SHOW
 COMPLIANCE WITH FBC ACC 604.8.1.2 AND 604.8.1.7
 ...F) SHOW TOE AND KNEE CLEARANCE FOR ACCESSIBLE
 LAVATORIES AS REQUIRED BY FBC ACC 306.2 AND 306.3
 ...G) KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED FOR THE DRINKING FOUNTAIN PER FBC ACC
 602.2.
 ...H) THE SPOUT FOR THE DRINKING FOUNTAIN SHALL BE
 LOCATED 15 INCHES (380 MM) MINIMUM FROM THE VERTICAL
 SUPPORT AND 5 INCHES (125 MM) MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
  
 2.PER WPB FBC 107.2.1, ADD NOTE TO P9.01, SECTION 2.01
 DOMESTIC WATER ?ALL FIXTURES AND COMPONENTS IN THE
 DOMESTIC WATER SYSTEM SHALL BE LEAD FREE?
  
 3.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 4.PROVIDE DETAIL FOR STRUCTURAL SUPPORT OF SUSPENDED
 WATER HEATER PER WPB FBC 107.2.1. DETAIL SHALL INCLUDE
 BUT IS NOT LIMITED TO, ROD SIZE, SIZE AND TYPE OF
 ANCHORS, BEAM CLAMPS, MATERIAL AND THICKNESS OF
 PLATFORM, PLATFORM DIMENSIONS AND HEIGHT ABOVE THE
 FLOOR TO BOTTOM OF THE ASSEMBLY.
  
 5.PER WPB FBC107.2.1, PROVIDE RATED WALL/FLOOR DETAILS
 FOR PIPE PENETRATIONS COMPLYING WITH FBC CHPT. 7
  
 6.SEE M302 SHOWING CONDENSATE TO THE MOP RECEPTACLE.
 PER WPB CODE OF ORDINANCE CHAPTER 90, ARTICLE 3,
 SECTION 90-12B5, A/C CONDENSATE (INTERPRET THIS AS ANY
 CONDENSATION FROM EVAPORATOR COILS) SHALL NOT DISCHARGE
 TO THE CITY UTILITIES SANITARY SEWAGE INFRASTRUCTURE
 WITHOUT PERMISSION FROM THE UTILITIES DEPARTMENT.
 MOVING FORWARD, DISCHARGE THE CONDENSATE TO AN EXTERIOR
 DRYWELL OR TO THE STORM SYSTEM; PER WPB FBC 107.2.1 AND
 FBC PL SECTION 314, PROVIDE ROUTING AND CONNECTION
 DETAIL AT THE POINT OF DISCHARGE.
  
 7.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TRAP PRIMER
 FROM WATER SOURCE TO THE FLOOR SINK.
  
 8.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TEMPERED
 WATER TO LAVATORIES SHOWING COMPLIANCE WITH FBC PL
 419.5
  
 9.PER WPB FBC 107.2.1, PROVIDE A SCHEDULE AND SHOW
 LOCATIONS OF EQUIPMENT REQUIRING PLUMBING CONNECTIONS
 INCLUDING, BUT NOT LIMITED TO WATER FILTERS, ICE
 MACHINES/MAKERS, BEVERAGE MACHINES AND COFFEE MAKER.
 SPECIFY ON THE SCHEDULE THE APPROPRIATE METHOD OF
 BACKFLOW PREVENTION AND BACKFLOW PREVENTION DEVICE,
 COMPLYING WITH FBC PL SECTION 608.
  
 10.PER WPB FBC 107.2.1, PROVIDE DETAIL OF EACH PIECE OF
 EQUIPMENT REQUIRING PLUMBING CONNECTIONS INCLUDING, BUT
 NOT LIMITED TO WATER FILTERS, ICE MACHINES/MAKERS,
 BEVERAGE MACHINES AND COFFEE MAKER. SHOW COMPLIANCE
 WITH FBC PL SECTION 608
  
 11.THE INDIVIDUAL VENTS FOR THE WATER CLOSETS, FLOOR
 SINK AND THE MOP RECEPTACLE ARE NOT COMPLIANT. VENTS
 SHALL CONNECT ABOVE THE CENTERLINE OF THE DRAIN OF THE
 HORIZONTAL DRAIN AND SHALL RISE VERTICALLY TO A POINT
 NOT LESS THAN 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED PER FBC PL
 905.3 AND 905.4.
  
 12.PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTORS FOR
 QUICK CLOSING VALVES IN THE DOMESTIC WATER SYSTEM.
 INDICATE THE REQUIRED LOCATIONS ON THE PLANS. WATER
 HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  