2021-10-15 06:16:361ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090944
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE SUITE NUMBER ON THE DRAWINGS FOR
 THIS TENANT SPACE. FBC 107.2.1
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1 &
 TABLE 403.3.1.1
  
 3) SHEET M202: PLEASE EXPLAIN THE EXISTING 20 X 16 OA
 DUCT, IS THIS GOING UP TO THE ROOF TO A UNIT THAT IS
 CONDITIONING THE AIR? FBC 107.2.1
  
 4) PLEASE EXPLAIN AND SHOW ON THE DRAWING HOW YOU ARE
 SUPPLYING THE OUTDOOR AIR TO EACH HEAT PUMP. FBC
 107.2.1
  
 5) PLEASE EXPLAIN THE 6 INCH DUCT COMING FROM THE
 BATHROOM AND DUMPING AIR INTO THE CORRIDORS. FBC M
 601.5-7
  
 6) PLEASE SHOW THE CFM?S THAT HEAT PUMP 4 IS SUPPLYING
 TO THE OFFICE SUPPLY GRILLES. FBC 107.2.1
  
 7) SHEET M202: PLEASE EXPLAIN THE EF-1 SHOWN IN THE
 BATHROOM, THERE IS NOTHING SHOWN BEING DUCTED TO THIS
 EF-1.
  
 8) SHEET M302: THE CONDENSATION FROM THE MECHANICAL
 SYSTEMS CANNOT TERMINATE INTO THE SANITARY SEWER
 SYSTEM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  