| 2021-10-15 06:16:36 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21090944 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE SUITE NUMBER ON THE DRAWINGS FOR |
| | THIS TENANT SPACE. FBC 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1 & |
| | TABLE 403.3.1.1 |
| | |
| | 3) SHEET M202: PLEASE EXPLAIN THE EXISTING 20 X 16 OA |
| | DUCT, IS THIS GOING UP TO THE ROOF TO A UNIT THAT IS |
| | CONDITIONING THE AIR? FBC 107.2.1 |
| | |
| | 4) PLEASE EXPLAIN AND SHOW ON THE DRAWING HOW YOU ARE |
| | SUPPLYING THE OUTDOOR AIR TO EACH HEAT PUMP. FBC |
| | 107.2.1 |
| | |
| | 5) PLEASE EXPLAIN THE 6 INCH DUCT COMING FROM THE |
| | BATHROOM AND DUMPING AIR INTO THE CORRIDORS. FBC M |
| | 601.5-7 |
| | |
| | 6) PLEASE SHOW THE CFM?S THAT HEAT PUMP 4 IS SUPPLYING |
| | TO THE OFFICE SUPPLY GRILLES. FBC 107.2.1 |
| | |
| | 7) SHEET M202: PLEASE EXPLAIN THE EF-1 SHOWN IN THE |
| | BATHROOM, THERE IS NOTHING SHOWN BEING DUCTED TO THIS |
| | EF-1. |
| | |
| | 8) SHEET M302: THE CONDENSATION FROM THE MECHANICAL |
| | SYSTEMS CANNOT TERMINATE INTO THE SANITARY SEWER |
| | SYSTEM. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |