Plan Review Notes
Plan Review Notes For Permit 21090852
Permit Number 21090852
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-08 10:22:282ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21090852
 10/8/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLUMBING COMMENTS FOR THE
 FOUNDATION PERMIT WERE EXTRACTED FROM THE 2ND REVIEW OF
 THE MAIN BUILDING PLANS UNDER PERMIT 21070675. THE
 COMMENTS ARE APPLICABLE TO BOTH PERMITS.
  
 12) FAILED P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A)
 FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION 1003.4.2 FBC P.
 PLEASE ADD THE SOI-1 TO THE SEPARATE PERMIT LIST ON
 SHEET G1.0.1. FAILED. C) PROVIDE SIZING CALCULATIONS IN
 ACCORDANCE WITH SECTION 1003.4.2.1 OR PER
 MANUFACTURER'S SPECIFICATIONS. IT APPEARS THAT THE
 SO1-1 CALCULATIONS HAVE BEEN MISLABELED AS LINT
 INTERCEPTOR CALCULATION. IF THAT IS THE CASE, IT ALSO
 APPEARS THAT THE OS-75 AT 93 GALLONS CAPACITY IS
 UNDERSIZED PER THE 110 GALLONS REQUIRED BY THE
 CALCULATIONS.
  
 13) FAILED. P1.1.0 LINT TRAP (LI-1): A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1003.6 FBC P. SEE COMMENT #12
 REGARDING THE LINT INTERCEPTOR SIZING CALCULATIONS.
 PLEASE CLARIFY HOW THE LINT INTERCEPTOR WAS SIZED.
  
 14) FAILED. P1.1.0 STORM SUMP PUMP: A) FAILED. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS- SECTION 1113.1 FBC P. PLEASE ADD THE SUMP
 PUMP COMPONENTS TO THE DEFERRED SUBMITTALS LIST ON
 G1.01. REVIEW COMMENT #16 NOTES BELOW.
  
 16) FAILED. P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING
 CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE
 BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE
 SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND
 VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER
 INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR
 ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM
 UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205
 WPB. PLEASE REFER TO SEC. 90-203-205 WPB CODE OF
 ORDINANCES- THE PLAN SHOWS TRENCH DRAINS FROM THE
 GARAGE DRAINING DIRECTLY INTO THE SUMP PIT, BUT NEARBY
 FLOOR DRAINS DRAINING INTO THE OIL SEPARATOR. PLEASE
 CLARIFY WHY THE DRAINAGE FROM THE FLOOR DRAINS WOULD
 CONTAIN SUBSTANCES THAT REQUIRE SEPARATION AND THE
 TRENCH DRAINS WOULD NOT. THE EOR SHALL VERIFY THAT THE
 DISCHARGE FROM THE SUMP INTO THE STORM DRAIN SYSTEM
 WILL CONTAIN ONLY STORMWATER AND NO OTHER SUBSTANCES
 SUCH AS OIL, GREASE, OR CHEMICALS. PLEASE NOTE THAT AN
 OIL SEPARATOR MAY BE REQUIRED- SEC. 1003.4 FBC P.
  
 17) FAILED- SEE NOTES. P1.1.0 SANITARY BACKWATER VALVE:
 A) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATIONS INSTRUCTIONS- SECTIONS 715.2- 715.4. NOT
 PROVIDED. PLEASE ADD THE VALVE TO THE DEFERRED
 SUBMITTALS LIST ON G1.01.B) FAILED. PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED.
  
 19) FAILED. P1.1.1 GREASE INTERCEPTOR. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED- DEFERRED UNDER
 SEPARATE PERMIT. D) FAILED. PLEASE NOTE ONLY FIXTURES
 DISCHARGING GREASE LADEN WASTE WATER SHALL FLOW INTO
 THE GREASE INTERCEPTOR. CLEAR WATER WASTE FROM HAND
 SINKS, ICE MACHINES ETC. SHALL NOT DRAIN INTO THE
 SYSTEM- SECTION 1003.3.1 FBC P. THE CALCULATIONS ON
 P5.02 SHOW BAR SINKS. PLEASE CLARIFY THE LOCATIONS OF
 BAR SINKS ON THE PLANS AND WHAT THEIR USES ARE- THEY
 ARE NOT SPECIFIED IN THE SCHEDULE.
  
 20) FAILED. P1.1.1 SOLIDS INTERCEPTOR S1-1: A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED. THE
 RESPONSE NARRATIVE INDICATES THE S1-1 SPECS LOCATED AT
 DETAIL 2 ON SHEET P5.02 HOWEVER DETAIL 2 IS THE STORM
 SUMP PUMP DETAIL. B) FAILED. PROVIDE SIZING
 CALCULATIONS- 1003.3.4. NOT PROVIDED. C) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB.
  
 21) FAILED. P1.1.1 SAMPLING PORT (SP-1): A) FAILED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED-
 PLEASE ADD TO THE DEFERRED SUBMITTALS LIST. B) FAILED.
 PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING-
 SECTION 107.2.1 WPB. NOT PROVIDED- PLEASE ADD TO THE
 DEFERRED SUBMITTALS LIST.
  
 22) FAILED. P1.1.1: PROVIDE NOTES AT THE TERMINATION
 LOCATIONS OF THE GREASE WASTE AND SANITARY SEWER LINES
 OR SHOW THE POINTS OF CONNECTIONS TO THE SEWER LINE-
 SECTION 107.2.1 WPB. SHEET C3.1 SHOWS A SEWER
 CONNECTION AT THE LIFT STATION FOR THE STORM DRAINAGE-
 PLEASE CORRECT.
  
 23) FAILED. P1.1.1 STORM WATER BACKWATER VALVE: A)
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS
 INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN
 INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS
 715.5 & 305.7. NOT PROVIDED. PLEASE ADD TO THE DEFERRED
 SUBMITTALS LIST.
  
 26) FAILED. P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE
 MOP SINK IS SHOWN TO BE CONNECTING TO THE SANITARY
 DRAIN- SECTION 1003.3.1 FBC P. THE GREASE WASTE
 ISOMETRIC IS MISSING FROM THE DRAWINGS.
  
 27) FAILED. P4.01, P4.02, P7.01, P7.02, K7, K8, & K9:
 CLEAR WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE
 RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN
 DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED-
 SECTION 1003.3.1 FBC P. THE GREASE WASTE ISOMETRIC IS
 MISSING FROM THE DRAWINGS.
  
 28) FAILED. P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX
 EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. REFER TO
 SHEETS P.401 & P.702 AND CLARIFY HOW THE CONDENSATE
 WILL BE DISPOSED OF. SHOW THE CONDENSATE LINES FROM THE
 EVAPORATORS AND DISCHARGE LOCATIONS. IT APPEARS THAT
 HUB DRAINS CANNOT BE USED BECAUSE THEY MAY BE CONVEYING
 OTHER WASTE AND NOT JUST CONDENSATE. PLEASE NOTE THAT
 P.4021 SHOWS THE HUB DRAINS CONNECTING TO THE STORM,
 AND P.702 SHOWS CONNECTION TO THE SANITARY.
  
 32) FAILED. P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM
 DO NOT APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW
 THE FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P.
 A) RELOCATE THE 2-INCH VENT FOR BETWEEN THE TWO L2
 DRAIN CONNECTIONS- SECTION 912.2.1 FBC P. B) PROVIDE AN
 INDIVIDAUL VENT FOR SH-2- SECTION 910.1 FBC P. C)
 RELOCATE THE SH-1 SHOWER VENT TO A LOCATION BETWEEN THE
 TWO MOST UPSTREAM FIXTURES CONNECTING TO THE HORIZONTAL
 BRANCH- SECTION 912.2.1 FBC P.
  
 33) FAILED. P7.01 & P7.02: INDICATE HOW TRAP SEAL
 PROTECTION WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER
 TRAP SEALS SUBJECT TO EVAPORATION WILL BE PROTECTED-
 SECTION 1002.4.1 FBC P. THE CHIEF PLUMBING INSPECTOR
 FOR THE CITY OF WPB BUILDING DEPT. HAS PROHIBITED THE
 USE OF BARRIER-TYPE TRAP SEALS IN AREAS SUCH AS
 COMMERCAIL KITCHENS AND OTHER FLOOR AREAS WHERE
 EXCESSIVE GREASE OR OTHER SUBSTANCES AND DEBRIS WILL
 CAUSE THE TRAP TO FAIL. PLEASE PROVIDE AN ACCEPTABLE
 MEANS IN THE KITCHEN, BASEMENT AND LAUNDRY AREAS.
  
 38) FAILED. P.7.04: PROVIDE AN ENLARGED WATER
 FILTRATION PIPING DETAIL SHOWING SUPPLY CONNECTION TO
 THE FILTER, AND SUPPLY LINES TO FIXTURES AND EQUIPMENT
 REQUIRING FILTRATION. PLEASE NOTE THAT BACKFLOW
 PREVENTERS ARE REQUIRED FOR THE WATER SUPPLY LINES IN
 AND OUT OF THE FILTER- SECTION 608.3 FBC P. THE
 REQUESTED ENLARGED FILTER PIPING PLAN NOT PROVIDED. THE
 ISOMETRIC DRAWING APPEARS TO SHOW THE LOCATION OF THE
 FILTER BUT NO SUPPLY LINES TO EQUIPMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  