Plan Review Notes
Plan Review Notes For Permit 21090829
Permit Number 21090829
Review Stop G
Sequence Number 3
Notes
Date Text
2021-10-23 12:14:543RD REVIEW FBC-2020 GAS
 PERMIT-21090829
 10/23/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. THE ONE SUBMITTED IT BELONGS TO
 ENGPLANS LLC, AND IT CLEARLY SAYS IT SHALL NOT BE
 REPRODUCED IN A HOLE OR PART. THE COPY OF THE TIE-DOWN
 IS NOT ACCEPTABLE. VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT.
  
 2. CLEARLY INDICATE ON THE SURVEY IF THE SHELL FOR THE
 TANK IS 18 IN. BELOW GRADE HOW FAR FROM THE DRIVEWAY
 PER THE NFPA 58 SECTION 6.8.6.1?
  
 3. THERE IS A GRILL ON THE LP SYSTEM DOWN STREAM OF THE
 GENERATOR AND NOT IN THE CALCULATION OR SHOWN ON THE
 ISOMETRIC WOULD YOU PLEASE CORRECT BY ADDING IT WITH
 THE BTU'S AND THE LOCATION PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. WOULD YOU PLEASE PROVIDE HOW LP TANK IS TIE-DOWN AND
 WHAT METHOD, IF YOU ARE USING STRAPS OR CABLE, IF CABLE
 HOW IS IT PROTECTED FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58, BELOW GROUND IT SHALL BE ANCHORED PER NFPA
 58 SEC.3-2.2.7 (H). SHOW THE DEPTH OF THE LP GAS
 CONTAINER BELOW GRADE TO COMPLY WITH NFPA 58 SEC.
 6.6.6.1.
 MAY VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY
 BE ABLE TO PROVIDE THIS DOCUMENT.
  
 5. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 6. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF
 VALVES, THE PIPE USED, DISTANCE, LINE SIZE, AND
 PRESSURE.
  
 7. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND
 GENERATOR PER THE 2020 FBC RES. SEC.G2408.1.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 9. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?)
 FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  