| 2021-10-22 09:01:38 | 10/22/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS |
| | SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE |
| | DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE |
| | CODE SEC. 61G15-23.005. THE ONE SUBMITTED IT BELONGS TO |
| | ENGPLANS LLC, AND IT CLEARLY SAYS IT SHALL NOT BE |
| | REPRODUCED IN A HOLE OR PART. THE COPY OF THE TIE-DOWN |
| | IS NOT ACCEPTABLE. VISIT |
| | HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO |
| | PROVIDE THIS DOCUMENT. |
| | |
| | 2. WOULD YOU PLEASE SHOW ON THE SURVEY IF THE SHELL FOR |
| | THE TANK IS 18 IN. ABOVE GRADE, OR DOES IT REQUIRE |
| | VEHICULAR BARRIER PROTECTION BECAUSE IT IS BELOW GRADE |
| | AND HOW FAR FROM THE DRIVEWAY PER THE NFPA 58 SECTION |
| | 6.8.6.1? |
| | |
| | 3. THERE IS A GRILL ON THE LP SYSTEM DOWN STREAM OF THE |
| | GENERATOR AND NOT IN THE CALCULATION OR SHOWN ON THE |
| | ISOMETRIC WOULD YOU PLEASE CORRECT BY ADDING IT WITH |
| | THE BTU'S AND THE LOCATION PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |