| 2021-09-28 12:30:12 | 09/28/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE PROVIDE HOW LP TANK IS TIE-DOWN AND |
| | WHAT METHOD, IF YOU ARE USING STRAPS OR CABLE, IF CABLE |
| | HOW IS IT PROTECTED FOR THE LP TANK AND APPURTENANCES |
| | PER NFPA 58, BELOW GROUND IT SHALL BE ANCHORED PER NFPA |
| | 58 SEC.3-2.2.7 (H). SHOW THE DEPTH OF THE LP GAS |
| | CONTAINER BELOW GRADE TO COMPLY WITH NFPA 58 SEC. |
| | 6.6.6.1. |
| | MAY VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY |
| | BE ABLE TO PROVIDE THIS DOCUMENT. |
| | |
| | 2. PROVIDE THE UG TANK CLEARANCE DISTANCES IN |
| | MEASUREMENTS TO THE HOUSE, DRIVEWAY, AND PROPERTY LINE- |
| | SEE TABLE 6.4.1.1 AND SECTION 6.8.6.1 NFPA 58. PLEASE |
| | NOTE THAT IF THE TANK IS LESS TANK 10 FT. FROM THE |
| | DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18 IN. ABOVE |
| | GRADE, AND VEHICULAR BARRIER PROTECTION WILL BE |
| | REQUIRED. |
| | |
| | 3. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL GAS. |
| | |
| | A. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF |
| | VALVES, THE PIPE USED, DISTANCE, LINE SIZE, AND |
| | PRESSURE. |
| | |
| | B. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2. |
| | |
| | 5. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND |
| | GENERATOR PER THE 2020 FBC RES. SEC.G2408.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |