Plan Review Notes
Plan Review Notes For Permit 21090829
Permit Number 21090829
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-28 12:30:1209/28/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE HOW LP TANK IS TIE-DOWN AND
 WHAT METHOD, IF YOU ARE USING STRAPS OR CABLE, IF CABLE
 HOW IS IT PROTECTED FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58, BELOW GROUND IT SHALL BE ANCHORED PER NFPA
 58 SEC.3-2.2.7 (H). SHOW THE DEPTH OF THE LP GAS
 CONTAINER BELOW GRADE TO COMPLY WITH NFPA 58 SEC.
 6.6.6.1.
 MAY VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY
 BE ABLE TO PROVIDE THIS DOCUMENT.
  
 2. PROVIDE THE UG TANK CLEARANCE DISTANCES IN
 MEASUREMENTS TO THE HOUSE, DRIVEWAY, AND PROPERTY LINE-
 SEE TABLE 6.4.1.1 AND SECTION 6.8.6.1 NFPA 58. PLEASE
 NOTE THAT IF THE TANK IS LESS TANK 10 FT. FROM THE
 DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18 IN. ABOVE
 GRADE, AND VEHICULAR BARRIER PROTECTION WILL BE
 REQUIRED.
  
 3. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 A. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF
 VALVES, THE PIPE USED, DISTANCE, LINE SIZE, AND
 PRESSURE.
  
 B. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 5. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND
 GENERATOR PER THE 2020 FBC RES. SEC.G2408.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  