Plan Review Notes
Plan Review Notes For Permit 21090759
Permit Number 21090759
Review Stop G
Sequence Number 1
Notes
Date Text
2021-09-27 13:18:1309/27/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWING OF THE TIE-DOWN IS A COPY
 AND THE ORIGINAL SIGNED AND SEALED DOCUMENT. PLEASE SEE
 THE COMMENT ON THE SIGNATURE STOP FOR MORE INFORMATION.
 THE COPY OF THE TIE-DOWN IS NOT ACCEPTABLE. THE
 ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS SHALL
 PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE DOCUMENT-
 FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.005. OR YOU MAY VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT.
  
 2. THERE IS NO GENERATOR PERMIT OR APPLICATION FOR THE
 ADDRESS ON THE CITY RECORDS. A LICENSED CONTRACTOR IS
 REQUIRED FOR AN ELECTRICAL PERMIT ON THE GENERATOR PER
 THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 3. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS;
  
 A. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF
 VALVES, THE PIPE BEING USED, DISTANCE, LINE SIZE, AND
 PRESSURE.
  
 B. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 5. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) SHALL BE MONITORED
 PER THE NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE
 TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & THE NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT
 OF WATER TO ACTIVATE IT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  