| 2021-10-06 11:33:05 | 10/06/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SECOND REQUEST, A WASHING MACHINE HOOK-UP FOR THIS |
| | UNIT AS REQUIRED IN THE 2020 FBC SEC. P TABLE 403.1 |
| | |
| | 3. ON SHEET A-5B FOR THE SECOND FLOOR SHOWS A TANK-LESS |
| | WATER HEATER, AND THE LOCATION IS ON THE SECOND FLOOR |
| | IS NOT ACCESSIBLE FOR SERVICE PER MANUFACTURERS |
| | SPECIFICATION. WOULD YOU PLEASE PROVIDE A DIFFERENT |
| | LOCATION AND GIVE THE DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER? THE SITE OF |
| | THE WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. WOULD YOU PLEASE PLACE A NOTE ON PLANS? |
| | |
| | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. WOULD YOU PLEASE PLACE A NOTE ON |
| | PLANS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |